Worked example
Example: Illustrative 220 V machine at 50 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Supply voltage | 220.00 V |
| No-load line current | 4.0000 A |
| Shunt field current | 1.2000 A |
| Armature resistance (hot) | 0.25000 Ω |
| Load line current | 50.000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Constant losses (iron, friction, field) | 878.04 W |
| Efficiency as a motor | 86.605 % |
| Efficiency as a generator | 87.765 % |
| Armature current for maximum efficiency | 59.263 A |
Open this example in the calculator and change any input.
Formula
\(P_c = VI_0 - (I_0 - I_{sh})^2R_A, \quad \eta_m = \frac{VI_L - P_c - I_A^2R_A}{VI_L}, \quad \eta_g = \frac{VI_L}{VI_L + P_c + I_A^2R_A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Supply voltage | V |
| \(I_0\) | No-load line current | A |
| \(I_{sh}\) | Shunt field current | A |
| \(R_A\) | Armature resistance (hot) | Ω |
| \(I_L\) | Load line current | A |
| \(P_c\) | Constant losses (iron, friction, field) | W |
| \(\eta_m\) | Efficiency as a motor | - |
| \(\eta_g\) | Efficiency as a generator | - |
| \(I_{A,\eta max}\) | Armature current for maximum efficiency | A |
Method and standards
Swinburne test.
Where it is used
- DC machine testing and teaching.
- Estimating efficiency without a load bank.
Common mistakes
- Using cold armature resistance.
- Forgetting field current in armature current.
Assumptions and limits
- Constant losses unchanged with load; brush drop neglected.
References
- Swinburne (no-load) test
Questions and answers
Why is it called an indirect test?
Efficiency is calculated from losses, not measured by loading the machine.
Where is efficiency highest?
Where variable copper loss equals the constant losses.
What do the defaults represent?
An illustrative 220 V shunt machine taking 4 A light with 1.2 A field current and 0.25 Ω armature, evaluated at 50 A.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012), Say, Performance and Design of AC Machines, 3rd ed. (Pitman, 1958)