Worked example
Example: Illustrative 37 kW rewound motor. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Shaft output (load) | 37.000 kW |
| Efficiency before rewinding | 92.000 % |
| Efficiency drop after rewinding (points) | 1.5000 % |
| Running hours per year | 7,000.0 h |
| Electricity price per kWh | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Extra input power | 0.66659 kW |
| Extra energy per year | 4.6661 MWh |
| Extra cost per year | 37,329 |
Open this example in the calculator and change any input.
Formula
\(\Delta P = \frac{P}{\eta - \Delta\eta} - \frac{P}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Shaft output (load) | W |
| \(\eta\) | Efficiency before rewinding | - |
| \(\Delta\eta\) | Efficiency drop after rewinding (points) | - |
| \(t\) | Running hours per year | s |
| \(c\) | Electricity price per kWh | - |
| \(\Delta P\) | Extra input power | W |
| \(\Delta E\) | Extra energy per year | J |
| \(\Delta C\) | Extra cost per year | - |
Method and standards
Rewound motor.
Where it is used
- Motor repair decisions.
- Energy audit findings.
Common mistakes
- Assuming rewinding restores original efficiency.
- Ignoring running hours.
Assumptions and limits
- Same output before and after.
References
- Input-power difference from efficiency loss
- Bureau of Energy Efficiency
- Energy Efficiency in Electrical Utilities (Guide Book 3)
Questions and answers
What does a 1.5-point loss cost on a 37 kW motor?
About 0.67 kW, or 4.7 MWh a year at 7,000 h.
Should I rewind or replace?
If the extra cost of losses over a few years exceeds the price gap to a new efficient motor, replace.
What do the defaults represent?
An illustrative 37 kW load, 92 % efficient before rewinding, losing 1.5 points, 7,000 h a year at 8 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.