Rewound Motor Efficiency Loss: Extra Power and Cost

Extra input power and yearly cost caused by the efficiency lost when an induction motor is rewound, from load, original efficiency and the drop.

Inputs

Examples: Illustrative 37 kW rewound motorPoor rewind, 3 pointsGood rewind, half a point

Accepted: 0.1 to 100,000 kW
Accepted: 30 to 100 %
Accepted: 0 to 20 %
Accepted: 0 to 8,760 h
Accepted: 0 to 1,000

Results

Rewinding often lowers efficiency by 0.5–2 points, mainly from core damage when old windings are burnt out at too high a temperature and from changed winding geometry. Each point lost on a heavily used motor costs every year: compare that with the price difference between rewinding and buying a new, more efficient motor. Good rewind practice (controlled burn-out temperature, same wire and turns) keeps the loss small.

Extra input power0.66659kW
Extra energy per year4.6661MWh
Extra cost per year37,329

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 37 kW rewound motor. The inputs, in the units selected above:

InputValue
Shaft output (load)37.000 kW
Efficiency before rewinding92.000 %
Efficiency drop after rewinding (points)1.5000 %
Running hours per year7,000.0 h
Electricity price per kWh8.0000 -

Applying the formula below gives:

ResultValue
Extra input power0.66659 kW
Extra energy per year4.6661 MWh
Extra cost per year37,329

Open this example in the calculator and change any input.

Formula

\(\Delta P = \frac{P}{\eta - \Delta\eta} - \frac{P}{\eta}\)

Variables

Symbol Meaning SI unit
\(P\) Shaft output (load) W
\(\eta\) Efficiency before rewinding -
\(\Delta\eta\) Efficiency drop after rewinding (points) -
\(t\) Running hours per year s
\(c\) Electricity price per kWh -
\(\Delta P\) Extra input power W
\(\Delta E\) Extra energy per year J
\(\Delta C\) Extra cost per year -

Method and standards

Rewound motor.

Where it is used

  • Motor repair decisions.
  • Energy audit findings.

Common mistakes

  • Assuming rewinding restores original efficiency.
  • Ignoring running hours.

Assumptions and limits

  • Same output before and after.

References

  • Input-power difference from efficiency loss
  • Bureau of Energy Efficiency
  • Energy Efficiency in Electrical Utilities (Guide Book 3)

Questions and answers

What does a 1.5-point loss cost on a 37 kW motor?

About 0.67 kW, or 4.7 MWh a year at 7,000 h.

Should I rewind or replace?

If the extra cost of losses over a few years exceeds the price gap to a new efficient motor, replace.

What do the defaults represent?

An illustrative 37 kW load, 92 % efficient before rewinding, losing 1.5 points, 7,000 h a year at 8 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.