Motor Load from Measured Speed (Slip Method)

Estimated load of an induction motor from its measured speed, synchronous and rated full-load speeds and supply voltage, by the slip method used in energy audits.

Inputs

Examples: Illustrative 30 kW motor at 1482 rpmLow voltage, 6-pole2-pole pump motor

Accepted: 9.5493 to 9,549.3 rpm
Accepted: 9.5493 to 9,549.3 rpm
Accepted: 9.5493 to 9,549.3 rpm
Accepted: 1 to 30,000 V
Accepted: 1 to 30,000 V
Accepted: 0.1 to 100,000 kW

Results

Below full load an induction motor's slip is nearly proportional to its torque, so the load is about (measured slip/rated slip) × (V/V_r)², the voltage term correcting for slip falling as the square of voltage. It needs only a tachometer, so it is safe and quick for audits, but nameplate rated speeds are often rounded and rewound motors differ: treat the result as ±10–15 %. The input-power method is more accurate where power can be measured.

Measured slip1.2000%
Rated slip2.0000%
Estimated load60.000%
Estimated shaft output18.000kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 30 kW motor at 1482 rpm. The inputs, in the units selected above:

InputValue
Synchronous speed1,500.0 rpm
Rated full-load speed (nameplate)1,470.0 rpm
Measured speed1,482.0 rpm
Measured voltage415.00 V
Rated voltage415.00 V
Rated output30.000 kW

Applying the formula below gives:

ResultValue
Measured slip1.2000 %
Rated slip2.0000 %
Estimated load60.000 %
Estimated shaft output18.000 kW

Open this example in the calculator and change any input.

Formula

\(s = \frac{N_s - N}{N_s}, \quad f_L \approx \frac{s}{s_r}\left(\frac{V}{V_r}\right)^2\)

Variables

Symbol Meaning SI unit
\(N_s\) Synchronous speed rad/s
\(N_r\) Rated full-load speed (nameplate) rad/s
\(N\) Measured speed rad/s
\(V\) Measured voltage V
\(V_r\) Rated voltage V
\(P_r\) Rated output W
\(s\) Measured slip -
\(s_r\) Rated slip -
\(f_L\) Estimated load -
\(P\) Estimated shaft output W

Method and standards

Slip method.

Where it is used

  • Motor surveys in energy audits.
  • Finding underloaded motors.

Common mistakes

  • Trusting rounded nameplate speeds.
  • Using it on rewound motors without checking.

Assumptions and limits

  • Linear torque–slip region below full load.

References

  • Slip method of motor load estimation
  • Bureau of Energy Efficiency
  • Energy Efficiency in Electrical Utilities (Guide Book 3)

Questions and answers

What load is a 1470 rpm motor running at 1482 rpm?

About 60 % (slip 1.2 % against 2.0 % rated) at rated voltage.

Why correct for voltage?

At lower voltage the motor slips more for the same load, so slip alone would overstate the load.

What do the defaults represent?

An illustrative 30 kW, 4-pole motor rated 1470 rpm running at 1482 rpm at rated voltage.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.