Grid-Connected Induction Generator Output

Slip, power delivered, reactive power drawn and power factor of a grid-connected induction machine driven above synchronous speed, from its equivalent circuit.

Inputs

Examples: Illustrative 400 V machine at 1,530 rpmSmall hydro 6-pole at 1,015 rpmSame machine motoring at 1,470 rpm

Accepted: 100 to 15,000 V
Accepted: 10 to 400 Hz
Accepted: 2 to 48
Accepted: 9.5493 to 9,549.3 rpm
Accepted: 0.0001 to 100 Ω
Accepted: 0.0001 to 100 Ω
Accepted: 1 to 10,000 Ω
Accepted: 0.0001 to 100 Ω
Accepted: 0.0001 to 100 Ω

Results

Above synchronous speed the slip is negative and R₂′/s becomes a negative resistance: the machine returns real power to the grid while still drawing magnetising reactive power from it. Power is computed from the full equivalent circuit (stator impedance in series with the magnetising branch and rotor branch in parallel). Output rises roughly linearly with negative slip up to the pull-out point; reactive power is usually compensated with capacitors. Efficiency shows 0 if the machine is motoring.

Slip (negative when generating)2.0000%
Electrical power delivered to the grid-32.319kW
Reactive power drawn from the grid17.745kvar
Power factor0.87657
Mechanical input power-31.007kW
Efficiency0%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 400 V machine at 1,530 rpm. The inputs, in the units selected above:

InputValue
Line voltage (star)400.00 V
Frequency50.000 Hz
Number of poles4.0000 -
Shaft speed1,530.0 rpm
Stator resistance per phase0.080000 Ω
Stator leakage reactance0.35000 Ω
Magnetising reactance12.000 Ω
Rotor resistance referred0.090000 Ω
Rotor leakage reactance referred0.40000 Ω

Applying the formula below gives:

ResultValue
Slip (negative when generating)-2.0000 %
Electrical power delivered to the grid33.051 kW
Reactive power drawn from the grid18.943 kvar
Power factor0.86760
Mechanical input power34.452 kW
Efficiency95.933 %

Open this example in the calculator and change any input.

Formula

\(s = \frac{n_s - n}{n_s} < 0, \quad Z = R_1 + jX_1 + \frac{jX_M(R_2'/s + jX_2')}{R_2'/s + j(X_2' + X_M)}, \quad S = 3V_\phi I^*\)

Variables

Symbol Meaning SI unit
\(V_L\) Line voltage (star) V
\(f\) Frequency 1/s
\(p\) Number of poles -
\(n\) Shaft speed rad/s
\(R_1\) Stator resistance per phase Ω
\(X_1\) Stator leakage reactance Ω
\(X_M\) Magnetising reactance Ω
\(R_2'\) Rotor resistance referred Ω
\(X_2'\) Rotor leakage reactance referred Ω
\(s\) Slip (negative when generating) -
\(P_e\) Electrical power delivered to the grid W
\(Q\) Reactive power drawn from the grid var
\(\cos\varphi\) Power factor -
\(P_m\) Mechanical input power W
\(\eta\) Efficiency -

Method and standards

Induction generator.

Where it is used

  • Small hydro and wind generators.
  • Regenerative braking of induction motors.

Common mistakes

  • Using motor sign conventions for output.
  • Ignoring reactive power demand.

Assumptions and limits

  • Steady state; constant parameters; star connection; core loss neglected.

References

  • Induction machine equivalent circuit at negative slip

Questions and answers

Why does an induction generator need the grid?

It cannot make its own magnetising current; the grid (or capacitors) must supply reactive power.

How much faster than synchronous must it run?

Typically a few percent; rated output occurs near the rated motor slip, but negative.

What do the defaults represent?

An illustrative 400 V, 50 Hz, 4-pole machine driven at 1,530 rpm (2 % negative slip).

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.