Worked example
Example: Illustrative 400 V machine at 1,530 rpm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage (star) | 400.00 V |
| Frequency | 50.000 Hz |
| Number of poles | 4.0000 - |
| Shaft speed | 1,530.0 rpm |
| Stator resistance per phase | 0.080000 Ω |
| Stator leakage reactance | 0.35000 Ω |
| Magnetising reactance | 12.000 Ω |
| Rotor resistance referred | 0.090000 Ω |
| Rotor leakage reactance referred | 0.40000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Slip (negative when generating) | -2.0000 % |
| Electrical power delivered to the grid | 33.051 kW |
| Reactive power drawn from the grid | 18.943 kvar |
| Power factor | 0.86760 |
| Mechanical input power | 34.452 kW |
| Efficiency | 95.933 % |
Open this example in the calculator and change any input.
Formula
\(s = \frac{n_s - n}{n_s} < 0, \quad Z = R_1 + jX_1 + \frac{jX_M(R_2'/s + jX_2')}{R_2'/s + j(X_2' + X_M)}, \quad S = 3V_\phi I^*\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_L\) | Line voltage (star) | V |
| \(f\) | Frequency | 1/s |
| \(p\) | Number of poles | - |
| \(n\) | Shaft speed | rad/s |
| \(R_1\) | Stator resistance per phase | Ω |
| \(X_1\) | Stator leakage reactance | Ω |
| \(X_M\) | Magnetising reactance | Ω |
| \(R_2'\) | Rotor resistance referred | Ω |
| \(X_2'\) | Rotor leakage reactance referred | Ω |
| \(s\) | Slip (negative when generating) | - |
| \(P_e\) | Electrical power delivered to the grid | W |
| \(Q\) | Reactive power drawn from the grid | var |
| \(\cos\varphi\) | Power factor | - |
| \(P_m\) | Mechanical input power | W |
| \(\eta\) | Efficiency | - |
Method and standards
Induction generator.
Where it is used
- Small hydro and wind generators.
- Regenerative braking of induction motors.
Common mistakes
- Using motor sign conventions for output.
- Ignoring reactive power demand.
Assumptions and limits
- Steady state; constant parameters; star connection; core loss neglected.
References
- Induction machine equivalent circuit at negative slip
Questions and answers
Why does an induction generator need the grid?
It cannot make its own magnetising current; the grid (or capacitors) must supply reactive power.
How much faster than synchronous must it run?
Typically a few percent; rated output occurs near the rated motor slip, but negative.
What do the defaults represent?
An illustrative 400 V, 50 Hz, 4-pole machine driven at 1,530 rpm (2 % negative slip).
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)