Worked example
Example: Feedwater, 100 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water temperature | 100.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Saturation pressure | 1.0142 bar |
| Specific enthalpy | 419.10 kJ/kg |
| Specific entropy | 1.3070 kJ/(kg·K) |
| Density | 958.35 kg/m³ |
| Specific volume | 0.001043 m³/kg |
| Specific heat capacity | 4.2166 kJ/(kg·K) |
| Dynamic viscosity | 2.8159e-04 Pa·s |
| Kinematic viscosity | 2.9382e-07 m²/s |
| Thermal conductivity | 0.67722 W/(m·K) |
| Prandtl number | 1.7533 |
| Latent heat of vaporisation | 2,256.5 kJ/kg |
Open this example in the calculator and change any input.
Formula
Properties are evaluated from the IAPWS-IF97 equations, not from a fitted curve:
\(p_{sat} = p_s(T) \;\text{(IF97 Eq. 30)} \qquad h_f, s_f, v_f, c_p = f(p_{sat}, T) \;\text{(IF97 region 1)} \qquad h_{fg} = h_g - h_f\)
\(\nu = \frac{\mu}{\rho} \qquad Pr = \frac{c_p\,\mu}{k}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T\) | water temperature | K |
| \(p_{sat}\) | saturation (boiling) pressure at \(T\) | Pa |
| \(h_f\) | specific enthalpy of saturated liquid | J/kg |
| \(s_f\) | specific entropy of saturated liquid | J/(kg·K) |
| \(\rho\) | density | kg/m³ |
| \(v_f\) | specific volume | m³/kg |
| \(c_p\) | isobaric specific heat capacity | J/(kg·K) |
| \(\mu\) | dynamic viscosity | Pa·s |
| \(\nu\) | kinematic viscosity | m²/s |
| \(k\) | thermal conductivity | W/(m·K) |
| \(Pr\) | Prandtl number | – |
| \(h_{fg}\) | latent heat of vaporisation | J/kg |
Method and standards
Thermodynamic properties from the IAPWS Industrial Formulation 1997 (region 1 and the region 4 saturation line; region 3 by iteration above 350 °C). Viscosity from the IAPWS 2008 formulation and thermal conductivity from the IAPWS 2011 formulation, both evaluated at the IF97 density. The code is FireCAD's own implementation, verified against the check values printed in the IAPWS releases.
Where it is used
- Density and viscosity for pump and pipe calculations.
- Enthalpy for heat balances of hot water and feedwater.
- Specific heat and conductivity for heat-exchanger design.
Common mistakes
- Using 1000 kg/m³ for hot water: at 150 °C it is about 917 kg/m³.
- Ignoring pressure for hot water near boiling.
- Mixing dynamic and kinematic viscosity.
Assumptions and limits
- 0.01 °C to about 373.85 °C, just below the critical point (373.946 °C), where saturation properties are singular.
- The thermal conductivity omits the critical enhancement term of the IAPWS 2011 formulation: it reads about 0.2 % low for hot liquid near 200 °C and increasingly low towards the critical point. Viscosity near the critical point is also less certain.
- Pure water; dissolved solids change density and boiling point slightly.
References
- IAPWS R7-97(2012) IF97
- IAPWS R12-08 viscosity
- IAPWS R15-11 thermal conductivity
Questions and answers
Is the water at its saturation pressure or at atmospheric pressure?
At its saturation pressure, i.e. on the boiling line. Below 100 °C the difference from atmospheric-pressure water is negligible for density, viscosity and heat capacity (well under 0.1 %).
Why does the Prandtl number fall so steeply with temperature?
Viscosity drops by a factor of six between 20 °C and 150 °C while conductivity and heat capacity change little, so Pr = cp·μ/k falls from about 7 to about 1.1.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.