FireCADCalc

Steam Properties (IAPWS-IF97)

Phase, saturation temperature, enthalpy, entropy, density, specific heat, viscosity and conductivity of water or steam at a pressure and temperature.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)Desuperheater and PRDSBoiler attendant and boiler operator examinations

Inputs

Examples: Superheated steam, 10 bar / 250 °CMain steam, 100 bar / 540 °CFeedwater, 100 bar / 150 °CLow pressure steam, 0.5 bar / 100 °C

Absolute. Choose a gauge unit (bar g, psig) to enter gauge readings.

Results

StateSuperheated steam
Saturation temperature at p81.317°C
Degree of superheat18.683K
Specific enthalpy2,682.4kJ/kg
Specific entropy7.6952kJ/(kg·K)
Specific volume3.4188m³/kg
Density0.29250kg/m³
Specific heat capacity1.9732kJ/(kg·K)
Dynamic viscosity1.2286e-05Pa·s
Kinematic viscosity4.2002e-05m²/s
Thermal conductivity0.024357W/(m·K)
Prandtl number0.99529
Speed of sound474.97m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Superheated steam, 10 bar / 250 °C. The inputs, in the units selected above:

InputValue
Absolute pressure10.000 bar
Temperature250.00 °C

Applying the formula below gives:

ResultValue
StateSuperheated steam
Saturation temperature at p179.89 °C
Degree of superheat70.114 K
Specific enthalpy2,943.2 kJ/kg
Specific entropy6.9266 kJ/(kg·K)
Specific volume0.23274 m³/kg
Density4.2967 kg/m³
Specific heat capacity2.2116 kJ/(kg·K)
Dynamic viscosity1.8058e-05 Pa·s
Kinematic viscosity4.2029e-06 m²/s
Thermal conductivity0.040456 W/(m·K)
Prandtl number0.98720
Speed of sound550.11 m/s

Open this example in the calculator and change any input.

Formula

The state is located in the IAPWS-IF97 regions and the properties follow from the Gibbs or Helmholtz free energy of that region:

\(\text{region 1, 2, 5:}\; g(p, T) \quad\Rightarrow\quad v = \left(\frac{\partial g}{\partial p}\right)_T,\; h = g - T\left(\frac{\partial g}{\partial T}\right)_p,\; s = -\left(\frac{\partial g}{\partial T}\right)_p,\; c_p = -T\left(\frac{\partial^2 g}{\partial T^2}\right)_p\)

\(\text{region 3:}\; f(\rho, T) \;\text{with}\; p(\rho, T) = p \;\text{solved for}\; \rho \qquad \Delta T_{sh} = T - T_{sat}(p) \qquad \nu = \mu / \rho \qquad Pr = c_p \mu / k\)

Variables

Symbol Meaning SI unit
\(p\) absolute pressure Pa
\(T\) temperature K
\(\text{phase}\) compressed liquid, superheated steam or supercritical fluid –
\(T_{sat}\) saturation temperature at \(p\) K
\(\Delta T_{sh}\) degree of superheat (vapour only) K
\(h\) specific enthalpy J/kg
\(s\) specific entropy J/(kg·K)
\(v\) specific volume m³/kg
\(\rho\) density kg/m³
\(c_p\) isobaric specific heat capacity J/(kg·K)
\(\mu\) dynamic viscosity Pa·s
\(\nu\) kinematic viscosity m²/s
\(k\) thermal conductivity W/(m·K)
\(Pr\) Prandtl number –
\(w\) speed of sound m/s

Method and standards

FireCAD's own implementation of the IAPWS Industrial Formulation 1997 (IAPWS R7-97(2012)): regions 1, 2 and 5 from their Gibbs equations, region 3 from the Helmholtz equation with the density found by iteration, the saturation line from the region 4 equation. Transport properties from the IAPWS 2008 (viscosity) and 2011 (thermal conductivity) formulations at the IF97 density. Verified against the check values printed in the releases.

Where it is used

  • Heat balances of boilers, turbines, heat exchangers and steam users.
  • Steam pipe sizing (specific volume) and flow meter density compensation.
  • Checking the condition of steam from measured pressure and temperature.

Common mistakes

  • Entering gauge pressure where absolute pressure is needed.
  • Using old steam tables (IFC-67) and newer IF97 values side by side: the differences are small but show up in tests.
  • Reading saturated values when the steam is superheated, or the reverse.

Assumptions and limits

  • 0 to 800 °C up to 1 000 bar, and 800 to 2 000 °C up to 500 bar (IF97 range). Above 800 °C the transport properties are extrapolations.
  • The critical enhancement of viscosity and conductivity is omitted. It leaves the conductivity about 0.2 % low already for hot liquid near 200 °C and steam near 450 °C at 60–70 bar, and much more close to the critical point.
  • Pressures are absolute. Enter gauge readings with a gauge unit (bar g, kg/cm² g, psig) and the page adds one standard atmosphere.

References

  • IAPWS R7-97(2012) IF97
  • IAPWS R12-08 viscosity
  • IAPWS R15-11 thermal conductivity

Questions and answers

What is the degree of superheat?

The temperature above the saturation temperature at the same pressure, T − T_sat(p). Steam at 10 bar(a) and 250 °C is 70 K superheated because water boils at 179.9 °C at 10 bar.

What does "compressed liquid" mean?

Water below its boiling temperature at the given pressure. Its properties are close to those of saturated water at the same temperature, which is why older tables give only the saturated values.

What happens exactly at saturation?

On the saturation line the properties depend on the steam quality, not on pressure and temperature alone. The page then shows saturated-liquid properties with a warning; use the flash steam or saturated water calculators for wet steam.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.