FireCADCalc

Steam Blow-Off or Vent Line Flow (Choked Flow with Friction)

Steam flow from a vessel through a blow-off, vent or discharge pipe, from vessel pressure, pipe size and total resistance K, choked or subsonic.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)

Inputs

Examples: Ganapathy Q7.33: 170 psia saturated, 2 in. sch 40, K = 10 (book 12,630 lb/h)10 bar(a) to 5 bar(a) back pressure, DN50, K = 5 (subsonic)40 bar 400 °C start-up vent, DN100, K = 20

Results

Steam treated as a perfect gas with the γ entered (1.3) and the vessel specific volume from IAPWS-IF97; isentropic entry and adiabatic friction along the pipe. Ganapathy's tabulated method (Crane) gives results within a few per cent.

Superheated steam at the temperature entered.

Specific volume in the vessel0.073432m³/kg
Mach number at the pipe inlet0.18023
Steam flow44,049kg/h
Pressure at the pipe outlet plane6.5985bar
Choked at the outlet (1 = yes)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy Q7.33: 170 psia saturated, 2 in. sch 40, K = 10 (book 12,630 lb/h). The inputs, in the units selected above:

InputValue
Vessel pressure (absolute)11.721 bar
Steam temperature (≤ saturation = dry saturated)0 °C
Pressure at the pipe outlet (absolute)1.0132 bar
Pipe inside diameter52.502 mm
Total resistance (f_D L/d + fittings, velocity heads)10.000 -
Isentropic exponent of steam1.3000 -

Applying the formula below gives:

ResultValue
Specific volume in the vessel0.16697 m³/kg
Mach number at the pipe inlet0.24172
Steam flow5,503.7 kg/h
Pressure at the pipe outlet plane2.5551 bar
Choked at the outlet (1 = yes)1.0000

Open this example in the calculator and change any input.

Formula

\(\frac{f_DL^*}{d} = \frac{1 - M_1^2}{\gamma M_1^2} + \frac{\gamma + 1}{2\gamma}\ln\frac{(\gamma + 1)M_1^2}{2 + (\gamma - 1)M_1^2} = K\ \text{(choked)}\)

\(p_1 = p_0\left(1 + \frac{\gamma - 1}{2}M_1^2\right)^{-\gamma/(\gamma - 1)}, \quad W = M_1\sqrt{\gamma p_1\rho_1}\,\frac{\pi d^2}{4}\)

Variables

Symbol Meaning SI unit
\(p_0\) Vessel pressure (absolute) Pa
\(T_0\) Steam temperature (≤ saturation = dry saturated) K
\(p_b\) Pressure at the pipe outlet (absolute) Pa
\(d\) Pipe inside diameter m
\(K\) Total resistance (f_D L/d + fittings, velocity heads) -
\(\gamma\) Isentropic exponent of steam -
\(v_0\) Specific volume in the vessel m³/kg
\(M_1\) Mach number at the pipe inlet -
\(W\) Steam flow kg/s
\(p_2\) Pressure at the pipe outlet plane Pa
\(\text{choked}\) Choked at the outlet (1 = yes) -

Method and standards

Isentropic entry plus Fanno flow; subsonic case solved for the outlet pressure.

Where it is used

  • Start-up vents, blow-off and silencer lines.
  • Relief valve discharge piping checks.

Common mistakes

  • Using gauge pressure.
  • Leaving out entrance and exit losses from K.

Assumptions and limits

  • Perfect-gas steam with the γ you enter; adiabatic; no condensation or real-gas effects along the line (about 4 % below Ganapathy's Crane-based figure in his example).
  • Dry saturated or superheated steam only: a temperature at or below saturation is taken as dry saturated (a note says so); wet steam cannot be entered.

References

  • Ganapathy
  • Industrial Boilers and Heat Recovery Steam Generators (Marcel Dekker, 2003)
  • Q7.33 (flow in steam blow-off lines); Fanno-line relations; IAPWS-IF97 vessel state

Questions and answers

Why does flow stop rising as outlet pressure falls?

The pipe chokes: the steam reaches sonic speed at the outlet and lower downstream pressure no longer reaches back into the pipe.

What does Ganapathy's example give?

Saturated steam at 170 psia through 2 in. schedule 40 pipe with K = 10: about 12,100 lb/h (5.5 t/h) here; Ganapathy's tabulated (Crane) method gives 12,630 lb/h, 4 % higher.

What is K?

The total resistance in velocity heads: friction f_D·L/d plus entrance, fittings and exit.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.