Worked example
Example: Ganapathy Q7.33: 170 psia saturated, 2 in. sch 40, K = 10 (book 12,630 lb/h). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Vessel pressure (absolute) | 11.721 bar |
| Steam temperature (≤ saturation = dry saturated) | 0 °C |
| Pressure at the pipe outlet (absolute) | 1.0132 bar |
| Pipe inside diameter | 52.502 mm |
| Total resistance (f_D L/d + fittings, velocity heads) | 10.000 - |
| Isentropic exponent of steam | 1.3000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Specific volume in the vessel | 0.16697 m³/kg |
| Mach number at the pipe inlet | 0.24172 |
| Steam flow | 5,503.7 kg/h |
| Pressure at the pipe outlet plane | 2.5551 bar |
| Choked at the outlet (1 = yes) | 1.0000 |
Open this example in the calculator and change any input.
Formula
\(\frac{f_DL^*}{d} = \frac{1 - M_1^2}{\gamma M_1^2} + \frac{\gamma + 1}{2\gamma}\ln\frac{(\gamma + 1)M_1^2}{2 + (\gamma - 1)M_1^2} = K\ \text{(choked)}\)
\(p_1 = p_0\left(1 + \frac{\gamma - 1}{2}M_1^2\right)^{-\gamma/(\gamma - 1)}, \quad W = M_1\sqrt{\gamma p_1\rho_1}\,\frac{\pi d^2}{4}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_0\) | Vessel pressure (absolute) | Pa |
| \(T_0\) | Steam temperature (≤ saturation = dry saturated) | K |
| \(p_b\) | Pressure at the pipe outlet (absolute) | Pa |
| \(d\) | Pipe inside diameter | m |
| \(K\) | Total resistance (f_D L/d + fittings, velocity heads) | - |
| \(\gamma\) | Isentropic exponent of steam | - |
| \(v_0\) | Specific volume in the vessel | m³/kg |
| \(M_1\) | Mach number at the pipe inlet | - |
| \(W\) | Steam flow | kg/s |
| \(p_2\) | Pressure at the pipe outlet plane | Pa |
| \(\text{choked}\) | Choked at the outlet (1 = yes) | - |
Method and standards
Isentropic entry plus Fanno flow; subsonic case solved for the outlet pressure.
Where it is used
- Start-up vents, blow-off and silencer lines.
- Relief valve discharge piping checks.
Common mistakes
- Using gauge pressure.
- Leaving out entrance and exit losses from K.
Assumptions and limits
- Perfect-gas steam with the γ you enter; adiabatic; no condensation or real-gas effects along the line (about 4 % below Ganapathy's Crane-based figure in his example).
- Dry saturated or superheated steam only: a temperature at or below saturation is taken as dry saturated (a note says so); wet steam cannot be entered.
References
- Ganapathy
- Industrial Boilers and Heat Recovery Steam Generators (Marcel Dekker, 2003)
- Q7.33 (flow in steam blow-off lines); Fanno-line relations; IAPWS-IF97 vessel state
Questions and answers
Why does flow stop rising as outlet pressure falls?
The pipe chokes: the steam reaches sonic speed at the outlet and lower downstream pressure no longer reaches back into the pipe.
What does Ganapathy's example give?
Saturated steam at 170 psia through 2 in. schedule 40 pipe with K = 10: about 12,100 lb/h (5.5 t/h) here; Ganapathy's tabulated (Crane) method gives 12,630 lb/h, 4 % higher.
What is K?
The total resistance in velocity heads: friction f_D·L/d plus entrance, fittings and exit.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.