FireCADCalc

Combined Separating and Throttling Calorimeter

Dryness fraction of wet steam from a separating calorimeter followed by a throttling calorimeter: x = x₁ × x₂ from the water separated, the condensate and the throttled state.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerBoiler attendant and boiler operator examinations

Inputs

Examples: 10 kg/cm² g, 0.5 kg separated, 10 kg condensate, 1.013 bar at 115 °C12 bar(a), 1.5 kg, 20 kg, 1.1 bar at 112 °C8 bar g, 0.2 kg, 12 kg, 1.013 bar at 120 °C

Absolute: the barometric pressure when the calorimeter exhausts to air. The main pressure above may be typed as gauge; it is converted with the standard atmosphere.

Results

Dryness from the separator x₁ = m_c / (m_c + m_w)98.361%
Dryness from the throttling calorimeter97.211%
Dryness fraction of the steam x = x₁ x₂95.617%
Enthalpy of the steam in the main2,684.1kJ/kg
Superheat after throttling20.026K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 kg/cm² g, 0.5 kg separated, 10 kg condensate, 1.013 bar at 115 °C. The inputs, in the units selected above:

InputValue
Steam pressure in the main (absolute)9.8066 bar g
Water collected in the separator0.50000 kg
Condensate from the throttling calorimeter10.000 kg
Pressure after throttling (absolute)1.0132 bar
Temperature after throttling115.00 °C

Applying the formula below gives:

ResultValue
Dryness from the separator x₁ = m_c / (m_c + m_w)95.238 %
Dryness from the throttling calorimeter96.318 %
Dryness fraction of the steam x = x₁ x₂91.731 %
Enthalpy of the steam in the main2,614.5 kJ/kg
Superheat after throttling15.026 K

Open this example in the calculator and change any input.

Formula

\(x_1 = \frac{m_c}{m_c + m_w}\)

\(h_{f1} + x_2\, h_{fg1} = h(p_2, T_2)\)

\(x = x_1\, x_2, \quad h = h_{f1} + x\, h_{fg1}, \quad \Delta T_{sh} = T_2 - T_{sat}(p_2)\)

Variables

Symbol Meaning SI unit
\(p_1\) Steam pressure in the main (absolute) Pa
\(m_w\) Water collected in the separator kg
\(m_c\) Condensate from the throttling calorimeter kg
\(p_2\) Pressure after throttling (absolute) Pa
\(T_2\) Temperature after throttling K
\(x_1\) Dryness from the separator x₁ = m_c / (m_c + m_w) -
\(x_2\) Dryness from the throttling calorimeter -
\(x\) Dryness fraction of the steam x = x₁ x₂ -
\(h\) Enthalpy of the steam in the main J/kg
\(\Delta T_{sh}\) Superheat after throttling K
\(h_{f1}\), \(h_{fg1}\) saturated liquid enthalpy and latent heat at the main pressure J/kg
\(T_{sat}(p_2)\) saturation temperature after throttling K

Method and standards

Separator mass balance, then throttling at constant enthalpy into the superheated region; IAPWS-IF97 properties at the main and calorimeter states.

Worked example

Steam at 10 kg/cm² g: 0.5 kg of water is separated and 10 kg of condensate collected; after throttling the steam is at 1.013 bar and 115 °C.

  • x₁ = 10 / 10.5 = 0.952
  • h at 1.013 bar, 115 °C = 2706.3 kJ/kg; at 10.82 bar h_f = 778.0, h_fg = 2002.1 kJ/kg; x₂ = (2706.3 − 778.0)/2002.1 = 0.963
  • x = 0.952 × 0.963 = 0.917

Where it is used

  • Boiler attendant and operator examinations.
  • Measuring steam quality from boilers and in mains.

Common mistakes

  • Using the separator's dryness alone.
  • Using gauge pressure after the throttle.
  • Accepting a reading with almost no superheat (error grows).

Assumptions and limits

  • At least about 5 K of superheat after the throttle; a warning is given below that.
  • Heat loss from the calorimeter neglected; the pressure drop across the separator is neglected (the throttle inlet is taken at the main pressure).
  • x₂ above 1 is reported with a warning (the steam leaving the separator was superheated, or a reading is wrong).
  • The main pressure may be entered as gauge (converted with the standard atmosphere, 101.325 kPa); the pressure after throttling is absolute.

References

  • IAPWS-IF97 (water and steam)
  • Throttling at constant enthalpy (textbook)

Questions and answers

What dryness for 0.5 kg separated, 10 kg condensate, throttled to 1.013 bar at 115 °C from 10 kg/cm² g?

x₁ = 0.952 from the separator, x₂ = 0.963 from the throttling, so x = 0.917.

Why throttle the steam?

Throttling keeps the enthalpy constant. When the steam leaves superheated, its measured pressure and temperature fix that enthalpy, and so the dryness before the valve.

What if the throttled steam is not superheated?

Then its state is unknown from p and T: the steam was too wet, which is why the separator comes first.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.