Flash Steam Recovery Saving per Year

Flash steam recovered from hot condensate or blowdown in a flash vessel, the heat it carries and its value per year at your cost of steam (IAPWS-IF97).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)Flash vessel and condensate

Inputs

Examples: 5 t/h condensate 10 bar g to 1 bar g, 90 % usedBlowdown 1.2 t/h at 40 bar(a) to 0.5 bar g12 t/h at 17 bar g to 3.5 bar g, 80 %

Results

The value assumes each tonne of flash steam used replaces a tonne of boiler steam at the same cost; it is a little high where the flash steam is at lower pressure than the steam it replaces.

Flash fraction12.316%
Flash steam used1,182.4kg/h
Latent heat recovered696.23kW
Steam recovered per year8,276.6t
Value per year (your currency)1.8209e+07

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 t/h condensate 10 bar g to 1 bar g, 90 % used. The inputs, in the units selected above:

InputValue
Condensate pressure before the trap10.000 bar g
Flash vessel pressure1.0000 bar g
Condensate flow5,000.0 kg/h
Share of the flash steam actually used90.000 %
Operating hours per year8,000.0 h
Cost of steam per tonne (your currency)2,500.0 -

Applying the formula below gives:

ResultValue
Flash fraction12.534 %
Flash steam used564.02 kg/h
Latent heat recovered344.83 kW
Steam recovered per year4,512.1 t
Value per year (your currency)1.1280e+07

Open this example in the calculator and change any input.

Formula

\(x = \frac{h_{f1} - h_{f2}}{h_{fg2}} \qquad \dot m_{fs} = \dot m_c\,x\,u \qquad \dot Q = \dot m_{fs}\,h_{fg2} \qquad m_y = \dot m_{fs}\,t_y \qquad V_y = \frac{m_y}{1000\ \text{kg/t}}\,c_s\)

Variables

Symbol Meaning SI unit
\(p_1\) condensate pressure (absolute in SI; shown and entered as gauge, bar g) Pa
\(p_2\) flash vessel pressure (absolute in SI; shown and entered as gauge) Pa
\(\dot m_c\) condensate flow kg/s
\(u\) share used –
\(t_y\) hours per year s
\(c_s\) cost of steam per tonne currency
\(x\) flash fraction –
\(\dot m_{fs}\) flash steam used kg/s
\(\dot Q\) latent heat recovered W
\(m_y\) steam per year kg
\(V_y\) value per year currency
\(h_{f1}, h_{f2}, h_{fg2}\) IF97 enthalpies J/kg

Method and standards

Isenthalpic flashing of saturated liquid, IAPWS-IF97 enthalpies.

Where it is used

  • Condensate recovery schemes.
  • Blowdown heat recovery.
  • Deaerator steam reduction.

Common mistakes

  • Counting flash steam that is vented.
  • Using gauge pressure tables with absolute inputs.
  • Ignoring the drop in condensate return temperature.

Assumptions and limits

  • Saturated condensate at p_1; no subcooling.
  • Pressures are shown as gauge and converted with the standard atmosphere (101.325 kPa); at altitude the gauge reading differs slightly.
  • Each tonne of flash steam is valued as a tonne of boiler steam; where it replaces higher-pressure steam the value is a little high.

References

  • IAPWS-IF97

Questions and answers

What is flash steam from 5 t/h of condensate at 10 bar g to 1 bar g worth?

12.5 % flashes; using 90 % of it gives 564 kg/h, 4512 t a year at 8000 h, worth 11.3 million at 2500 per tonne.

Why value it at boiler steam cost?

Each tonne used replaces a tonne the boiler would make; it is slightly generous where flash replaces higher-pressure steam.

Where can flash steam be used?

Deaerator heating, air heaters, low-pressure process heating.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.