Worked example
Example: 6 t/h condensate at 85 °C, 4 t/h make-up at 30 °C, open tank. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Condensate return flow | 6,000.0 kg/h |
| Condensate temperature | 85.000 °C |
| Make-up water flow | 4,000.0 kg/h |
| Make-up water temperature | 30.000 °C |
| Feed tank pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Feedwater temperature | 63.036 °C |
| Condensate share of the feedwater | 60.000 % |
| Feedwater flow | 10,000 kg/h |
| Mixed enthalpy | 263.92 kJ/kg |
Open this example in the calculator and change any input.
Formula
\(h_m = \frac{\dot m_c\,h(T_c) + \dot m_{mu}\,h(T_{mu})}{\dot m_c + \dot m_{mu}} \qquad T_m = T(p, h_m) \quad \text{(all enthalpies at the tank pressure } p\text{)} \qquad r_c = \frac{\dot m_c}{\dot m_c + \dot m_{mu}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_c\) | condensate return flow | kg/s |
| \(T_c\) | condensate temperature | K |
| \(\dot m_{mu}\) | make-up water flow | kg/s |
| \(T_{mu}\) | make-up temperature | K |
| \(p\) | feed tank pressure, absolute | Pa |
| \(T_m\) | feedwater temperature | K |
| \(r_c\) | condensate share | – |
| \(\dot m_{fw}\) | feedwater flow, \(\dot m_c + \dot m_{mu}\) | kg/s |
| \(h_m\) | mixed enthalpy | J/kg |
| \(h\) | water enthalpy (IF97) | J/kg |
Method and standards
Adiabatic mixing; enthalpies and the outlet temperature from FireCAD's IAPWS-IF97.
Where it is used
- Estimating feed tank temperature for pump NPSH and oxygen removal.
- Valuing condensate return.
- Checking a feed tank heater duty.
Common mistakes
- Averaging temperatures without weighting by flow.
- Ignoring flash losses from hot condensate.
- Forgetting tank heat loss in winter.
Assumptions and limits
- No heat loss or steam heating in the tank; condensate taken as liquid at tank pressure. Condensate arriving from a higher line pressure is entered at its temperature in the tank; any flash is lost through the vent.
References
- IAPWS R7-97(2012) IF97
- first law of thermodynamics
Questions and answers
What temperature does the feed tank reach?
The flow-weighted enthalpy of the two streams. 6 t/h of condensate at 85 °C and 4 t/h of make-up at 30 °C mix to 63.0 °C.
How can I raise it?
Return more condensate, recover flash steam and blowdown heat to the tank, or heat it with exhaust or low-pressure steam. Each 6 K or so of feedwater temperature saves roughly 1 % of fuel in a typical shell boiler; the feedwater temperature saving calculator works it out for your case.
What if the condensate is above 100 °C?
It flashes in an open tank; the flash steam leaves through the vent. Enter it at the tank's boiling point and recover the flash separately.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.