Worked example
Example: 800 W/m², inlet 40 °C, ambient 30 °C, 2 m². The inputs, in the units selected above:
| Input | Value |
|---|---|
| Solar irradiance on the collector | 800.00 W/m² |
| Inlet water temperature | 40.000 °C |
| Ambient temperature | 30.000 °C |
| Optical intercept F_R(τα) | 75.000 % |
| Loss slope F_R U_L | 4.5000 W/(m²·K) |
| Collector aperture area | 2.0000 m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Efficiency | 69.375 % |
| Useful heat | 1,110.0 W |
| Reduced temperature | 0.012500 m²·K/W |
| Inlet temperature at zero output | 163.33 °C |
Open this example in the calculator and change any input.
Formula
\(\eta = F_R(\tau\alpha) - F_R U_L\,\frac{T_i - T_a}{G}, \quad \dot Q_u = \eta\, G\, A, \quad T_{stag} = T_a + \frac{F_R(\tau\alpha)\,G}{F_R U_L}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(G\) | Solar irradiance on the collector | W/m² |
| \(T_i\) | Inlet water temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(F_R(\tau\alpha)\) | Optical intercept F_R(τα) | - |
| \(F_R U_L\) | Loss slope F_R U_L | W/(m²·K) |
| \(A\) | Collector aperture area | m² |
| \(\eta\) | Efficiency | - |
| \(\dot Q_u\) | Useful heat | W |
| \((T_i - T_a)/G\) | Reduced temperature | m²·K/W |
| \(T_{stag}\) | Inlet temperature at zero output | K |
Method and standards
Hottel–Whillier–Bliss equation.
Where it is used
- Solar water heating design.
- Comparing collectors.
Common mistakes
- Using outlet instead of inlet temperature.
- Gross instead of aperture area.
Assumptions and limits
- Steady state, linear loss, on the inlet temperature. Test reports to ISO 9806 usually give η₀, a₁ and a₂ on the mean fluid temperature; those must be converted to F_R(τα) and F_R U_L before use here.
- With F_R U_L = 0 the zero-output temperature is not defined and is not shown.
References
- Hottel–Whillier–Bliss equation (Duffie and Beckman, Solar Engineering of Thermal Processes, ch. 6)
Questions and answers
800 W/m², inlet 40 °C, ambient 30 °C?
Efficiency 69.4 %; 1110 W from 2 m².
Why does efficiency fall with temperature?
Losses grow with the collector-to-ambient difference.
Where are F_R(τα) and F_R U_L found?
In the collector's certified test report.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.