Heat Loss Through a Pipe with Two Insulation Layers

Heat loss per metre and layer temperatures of a pipe with up to two layers of insulation, with inside and outside coefficients, by cylindrical resistances in series.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 6-inch steam line at 400 °C, 50 mm + 50 mm2-inch hot oil at 250 °C, one 40 mm layerChilled water 7 °C, 30 mm nitrile on 3-inch

Results

Heat loss per metre-10.707W/m
Pipe outer wall temperature7.0270°C
Interface between layers A and B32.139°C
Outer surface temperature32.139°C
Outer radius74.450mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 6-inch steam line at 400 °C, 50 mm + 50 mm. The inputs, in the units selected above:

InputValue
Fluid temperature inside400.00 °C
Ambient temperature30.000 °C
Inside coefficient1,000.0 W/(m²·K)
Outside coefficient (convection + radiation)10.000 W/(m²·K)
Pipe inside radius77.100 mm
Pipe outside radius84.150 mm
Pipe wall conductivity45.000 W/(m·K)
Insulation layer A thickness (inner)50.000 mm
Layer A conductivity0.060000 W/(m·K)
Insulation layer B thickness (outer)50.000 mm
Layer B conductivity0.040000 W/(m·K)

Applying the formula below gives:

ResultValue
Heat loss per metre143.06 W/m
Pipe outer wall temperature399.66 °C
Interface between layers A and B222.69 °C
Outer surface temperature42.364 °C
Outer radius184.15 mm

Open this example in the calculator and change any input.

Formula

\(q' = \frac{T_i - T_a}{\dfrac{1}{2\pi r_1 h_i} + \sum \dfrac{\ln(r_{j+1}/r_j)}{2\pi k_j} + \dfrac{1}{2\pi r_o h_o}}\)

Variables

Symbol Meaning SI unit
\(T_i\) Fluid temperature inside K
\(T_a\) Ambient temperature K
\(h_i\) Inside coefficient W/(m²·K)
\(h_o\) Outside coefficient (convection + radiation) W/(m²·K)
\(r_1\) Pipe inside radius m
\(r_2\) Pipe outside radius m
\(k_p\) Pipe wall conductivity W/(m·K)
\(t_a\) Insulation layer A thickness (inner) m
\(k_a\) Layer A conductivity W/(m·K)
\(t_b\) Insulation layer B thickness (outer) m
\(k_b\) Layer B conductivity W/(m·K)
\(q'\) Heat loss per metre W/m
\(T_w\) Pipe outer wall temperature K
\(T_{ab}\) Interface between layers A and B K
\(T_s\) Outer surface temperature K
\(r_o\) Outer radius m

Method and standards

Steady radial conduction.

Where it is used

  • Steam and hot-oil line insulation.
  • Heat transfer examinations.

Common mistakes

  • Plane-wall formula for thick insulation.
  • Conductivity at the wrong mean temperature.

Assumptions and limits

  • Steady, uniform layers; fixed h_o.
  • Interface and surface temperatures are not compared with the service limits of the layers: check T_ab against the inner layer's limit and the outer layer's rating.

References

  • Cylindrical conduction resistances in series (Incropera, DeWitt, Bergman and Lavine, Fundamentals of Heat and Mass Transfer, ch. 3)

Questions and answers

Why two layers?

A high-temperature inner layer protects a cheaper outer layer, which sees a lower temperature.

What sets the interface temperature?

The ratio of the layers' resistances.

Which outside coefficient?

Convection plus radiation. Here h_o is a fixed input: ISO 12241 gives values that depend on the surface temperature, so check h_o against the T_s found and repeat.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.