Worked example
Example: 6-inch steam line at 400 °C, 50 mm + 50 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid temperature inside | 400.00 °C |
| Ambient temperature | 30.000 °C |
| Inside coefficient | 1,000.0 W/(m²·K) |
| Outside coefficient (convection + radiation) | 10.000 W/(m²·K) |
| Pipe inside radius | 77.100 mm |
| Pipe outside radius | 84.150 mm |
| Pipe wall conductivity | 45.000 W/(m·K) |
| Insulation layer A thickness (inner) | 50.000 mm |
| Layer A conductivity | 0.060000 W/(m·K) |
| Insulation layer B thickness (outer) | 50.000 mm |
| Layer B conductivity | 0.040000 W/(m·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat loss per metre | 143.06 W/m |
| Pipe outer wall temperature | 399.66 °C |
| Interface between layers A and B | 222.69 °C |
| Outer surface temperature | 42.364 °C |
| Outer radius | 184.15 mm |
Open this example in the calculator and change any input.
Formula
\(q' = \frac{T_i - T_a}{\dfrac{1}{2\pi r_1 h_i} + \sum \dfrac{\ln(r_{j+1}/r_j)}{2\pi k_j} + \dfrac{1}{2\pi r_o h_o}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_i\) | Fluid temperature inside | K |
| \(T_a\) | Ambient temperature | K |
| \(h_i\) | Inside coefficient | W/(m²·K) |
| \(h_o\) | Outside coefficient (convection + radiation) | W/(m²·K) |
| \(r_1\) | Pipe inside radius | m |
| \(r_2\) | Pipe outside radius | m |
| \(k_p\) | Pipe wall conductivity | W/(m·K) |
| \(t_a\) | Insulation layer A thickness (inner) | m |
| \(k_a\) | Layer A conductivity | W/(m·K) |
| \(t_b\) | Insulation layer B thickness (outer) | m |
| \(k_b\) | Layer B conductivity | W/(m·K) |
| \(q'\) | Heat loss per metre | W/m |
| \(T_w\) | Pipe outer wall temperature | K |
| \(T_{ab}\) | Interface between layers A and B | K |
| \(T_s\) | Outer surface temperature | K |
| \(r_o\) | Outer radius | m |
Method and standards
Steady radial conduction.
Where it is used
- Steam and hot-oil line insulation.
- Heat transfer examinations.
Common mistakes
- Plane-wall formula for thick insulation.
- Conductivity at the wrong mean temperature.
Assumptions and limits
- Steady, uniform layers; fixed h_o.
- Interface and surface temperatures are not compared with the service limits of the layers: check T_ab against the inner layer's limit and the outer layer's rating.
References
- Cylindrical conduction resistances in series (Incropera, DeWitt, Bergman and Lavine, Fundamentals of Heat and Mass Transfer, ch. 3)
Questions and answers
Why two layers?
A high-temperature inner layer protects a cheaper outer layer, which sees a lower temperature.
What sets the interface temperature?
The ratio of the layers' resistances.
Which outside coefficient?
Convection plus radiation. Here h_o is a fixed input: ISO 12241 gives values that depend on the surface temperature, so check h_o against the T_s found and repeat.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.