Worked example
Example: Counterflow water-water, 2 kg/s at 90 °C, 3 kg/s at 30 °C, UA 12 kW/K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow arrangement | Counterflow |
| Hot fluid flow | 7,200.0 kg/h |
| Hot fluid specific heat | 4.1900 kJ/(kg·K) |
| Hot fluid inlet temperature | 90.000 °C |
| Cold fluid flow | 10,800 kg/h |
| Cold fluid specific heat | 4.1800 kJ/(kg·K) |
| Cold fluid inlet temperature | 30.000 °C |
| Overall heat transfer coefficient | 1,200.0 W/(m²·K) |
| Heat transfer area | 10.000 m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Number of transfer units | 1.4320 |
| Heat capacity rate ratio C_min/C_max | 0.66826 |
| Effectiveness | 64.702 % |
| Heat duty | 325.32 kW |
| Hot fluid outlet temperature | 51.179 °C |
| Cold fluid outlet temperature | 55.943 °C |
Open this example in the calculator and change any input.
Formula
\(NTU = \frac{UA}{C_{min}}, \quad C_r = \frac{C_{min}}{C_{max}}\)
\(\varepsilon = \frac{1 - e^{-NTU(1 - C_r)}}{1 - C_r e^{-NTU(1 - C_r)}} \ \text{(counterflow; others from Table 11.3)}\)
\(\text{parallel: } \varepsilon = \frac{1 - e^{-NTU(1 + C_r)}}{1 + C_r} \qquad \text{one shell pass: } \varepsilon = 2\left[1 + C_r + \sqrt{1 + C_r^2}\,\frac{1 + e^{-NTU\sqrt{1 + C_r^2}}}{1 - e^{-NTU\sqrt{1 + C_r^2}}}\right]^{-1}\) \(\text{cross, both unmixed: } \varepsilon = 1 - \exp\left[\frac{NTU^{0.22}}{C_r}\left(e^{-C_r NTU^{0.78}} - 1\right)\right]\) \(\text{cross, } C_{max}\text{ mixed: } \varepsilon = \frac{1}{C_r}\left[1 - e^{-C_r(1 - e^{-NTU})}\right] \qquad \text{cross, } C_{min}\text{ mixed: } \varepsilon = 1 - \exp\left[-\frac{1 - e^{-C_r NTU}}{C_r}\right]\) \(C_r = 0:\ \varepsilon = 1 - e^{-NTU}\ (\text{all}), \qquad C_r = 1\ \text{counterflow: } \varepsilon = \frac{NTU}{1 + NTU}\) \(Q = \varepsilon\, C_{min} (T_{h,i} - T_{c,i})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{arr}\) | flow arrangement | - |
| \(\dot m_h\) | hot fluid flow | kg/s |
| \(c_{p,h}\) | hot fluid specific heat | J/(kg·K) |
| \(T_{h,i}\) | hot inlet temperature | K |
| \(\dot m_c\) | cold fluid flow | kg/s |
| \(c_{p,c}\) | cold fluid specific heat | J/(kg·K) |
| \(T_{c,i}\) | cold inlet temperature | K |
| \(U\) | overall coefficient | W/(m²·K) |
| \(A\) | area | m² |
| \(C_{min}\) | smaller heat capacity rate | W/K |
| \(C_{max}\) | larger heat capacity rate | W/K |
| \(NTU\) | number of transfer units | - |
| \(C_r\) | capacity rate ratio | - |
| \(\varepsilon\) | effectiveness | - |
| \(Q\) | duty | W |
| \(T_{h,o}\) | hot outlet temperature | K |
| \(T_{c,o}\) | cold outlet temperature | K |
Method and standards
Effectiveness is the actual duty over the most the smaller-capacity stream could transfer. For each arrangement it depends only on NTU and C_r, by the relations in Incropera's Table 11.3. The outlet temperatures then follow from energy balances.
Where it is used
- Rating an existing exchanger at new flows or temperatures.
- Checking whether extra area is worth it (diminishing returns at high NTU).
- Comparing flow arrangements.
Common mistakes
- Using the larger capacity rate for NTU.
- Applying the counterflow relation to a multi-pass shell-and-tube.
- Forgetting fouling in U.
Assumptions and limits
- Constant U and specific heats; no phase change except the C_r = 0 case.
References
- ε–NTU relations (Incropera, Fundamentals of Heat and Mass Transfer, Table 11.3)
Questions and answers
When use ε–NTU instead of LMTD?
When the outlet temperatures are unknown, as when rating an existing exchanger: ε–NTU gives them directly without iteration.
What does a counterflow exchanger with NTU 1.43 achieve?
With C_r 0.67, an effectiveness of about 65 %: in the example 325 kW from 90 °C water into 30 °C water.
Why is counterflow best?
It keeps a temperature difference along the whole length, so it approaches the full possible duty as NTU rises.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.