Heat Exchanger Effectiveness and Outlet Temperatures (ε–NTU)

Duty and outlet temperatures of an existing heat exchanger from UA and the inlet conditions, by the effectiveness–NTU method for six flow arrangements.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserEconomiser and air preheater

Inputs

Examples: Counterflow water-water, 2 kg/s at 90 °C, 3 kg/s at 30 °C, UA 12 kW/KShell and tube oil cooler, oil 5 kg/s at 120 °C, water 4 kg/s at 32 °CAir-cooled cross-flow, both unmixed: air 8 kg/s, water 2 kg/s at 80 °C

Results

The both-unmixed cross-flow relation is an approximation (exact for C_r = 1 only within a few per cent).

Number of transfer units1.6758
Heat capacity rate ratio C_min/C_max0.96134
Effectiveness58.880%
Heat duty213.45kW
Hot fluid outlet temperature54.528°C
Cold fluid outlet temperature61.496°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Counterflow water-water, 2 kg/s at 90 °C, 3 kg/s at 30 °C, UA 12 kW/K. The inputs, in the units selected above:

InputValue
Flow arrangementCounterflow
Hot fluid flow7,200.0 kg/h
Hot fluid specific heat4.1900 kJ/(kg·K)
Hot fluid inlet temperature90.000 °C
Cold fluid flow10,800 kg/h
Cold fluid specific heat4.1800 kJ/(kg·K)
Cold fluid inlet temperature30.000 °C
Overall heat transfer coefficient1,200.0 W/(m²·K)
Heat transfer area10.000 m²

Applying the formula below gives:

ResultValue
Number of transfer units1.4320
Heat capacity rate ratio C_min/C_max0.66826
Effectiveness64.702 %
Heat duty325.32 kW
Hot fluid outlet temperature51.179 °C
Cold fluid outlet temperature55.943 °C

Open this example in the calculator and change any input.

Formula

\(NTU = \frac{UA}{C_{min}}, \quad C_r = \frac{C_{min}}{C_{max}}\)

\(\varepsilon = \frac{1 - e^{-NTU(1 - C_r)}}{1 - C_r e^{-NTU(1 - C_r)}} \ \text{(counterflow; others from Table 11.3)}\)

\(\text{parallel: } \varepsilon = \frac{1 - e^{-NTU(1 + C_r)}}{1 + C_r} \qquad \text{one shell pass: } \varepsilon = 2\left[1 + C_r + \sqrt{1 + C_r^2}\,\frac{1 + e^{-NTU\sqrt{1 + C_r^2}}}{1 - e^{-NTU\sqrt{1 + C_r^2}}}\right]^{-1}\) \(\text{cross, both unmixed: } \varepsilon = 1 - \exp\left[\frac{NTU^{0.22}}{C_r}\left(e^{-C_r NTU^{0.78}} - 1\right)\right]\) \(\text{cross, } C_{max}\text{ mixed: } \varepsilon = \frac{1}{C_r}\left[1 - e^{-C_r(1 - e^{-NTU})}\right] \qquad \text{cross, } C_{min}\text{ mixed: } \varepsilon = 1 - \exp\left[-\frac{1 - e^{-C_r NTU}}{C_r}\right]\) \(C_r = 0:\ \varepsilon = 1 - e^{-NTU}\ (\text{all}), \qquad C_r = 1\ \text{counterflow: } \varepsilon = \frac{NTU}{1 + NTU}\) \(Q = \varepsilon\, C_{min} (T_{h,i} - T_{c,i})\)

Variables

Symbol Meaning SI unit
\(\text{arr}\) flow arrangement -
\(\dot m_h\) hot fluid flow kg/s
\(c_{p,h}\) hot fluid specific heat J/(kg·K)
\(T_{h,i}\) hot inlet temperature K
\(\dot m_c\) cold fluid flow kg/s
\(c_{p,c}\) cold fluid specific heat J/(kg·K)
\(T_{c,i}\) cold inlet temperature K
\(U\) overall coefficient W/(m²·K)
\(A\) area m²
\(C_{min}\) smaller heat capacity rate W/K
\(C_{max}\) larger heat capacity rate W/K
\(NTU\) number of transfer units -
\(C_r\) capacity rate ratio -
\(\varepsilon\) effectiveness -
\(Q\) duty W
\(T_{h,o}\) hot outlet temperature K
\(T_{c,o}\) cold outlet temperature K

Method and standards

Effectiveness is the actual duty over the most the smaller-capacity stream could transfer. For each arrangement it depends only on NTU and C_r, by the relations in Incropera's Table 11.3. The outlet temperatures then follow from energy balances.

Where it is used

  • Rating an existing exchanger at new flows or temperatures.
  • Checking whether extra area is worth it (diminishing returns at high NTU).
  • Comparing flow arrangements.

Common mistakes

  • Using the larger capacity rate for NTU.
  • Applying the counterflow relation to a multi-pass shell-and-tube.
  • Forgetting fouling in U.

Assumptions and limits

  • Constant U and specific heats; no phase change except the C_r = 0 case.

References

  • ε–NTU relations (Incropera, Fundamentals of Heat and Mass Transfer, Table 11.3)

Questions and answers

When use ε–NTU instead of LMTD?

When the outlet temperatures are unknown, as when rating an existing exchanger: ε–NTU gives them directly without iteration.

What does a counterflow exchanger with NTU 1.43 achieve?

With C_r 0.67, an effectiveness of about 65 %: in the example 325 kW from 90 °C water into 30 °C water.

Why is counterflow best?

It keeps a temperature difference along the whole length, so it approaches the full possible duty as NTU rises.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.