Swimming Pool Evaporation Rate and Latent Load

Evaporation from an indoor pool from surface area, water and air temperatures, humidity, air speed and activity factor, with the latent load and daily water loss.

Process steam and utilitiesFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: Hotel pool 300 m², 28/30 °C, 60 %Public pool 500 m², 27/29 °C, 55 %

Results

ASHRAE pool equation (w_p in kg/s with p in kPa, Y in kJ/kg). Activity factors: residential 0.5, hotel 0.8, public pools 1.0, whirlpools 1.0, wave pools 1.5. Keep room air 1–2 K above water to limit evaporation.

Evaporation rate101.41kg/h
Latent heat load68.647kW
Water lost per day2,433.8L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Hotel pool 300 m², 28/30 °C, 60 %. The inputs, in the units selected above:

InputValue
Pool surface area300.00 m²
Water temperature28.000 °C
Room air temperature30.000 °C
Room relative humidity60.000 %
Air velocity over the water0.10000 m/s
Activity factor0.80000 -

Applying the formula below gives:

ResultValue
Evaporation rate42.428 kg/h
Latent heat load28.693 kW
Water lost per day1,018.3 L

Open this example in the calculator and change any input.

Formula

\(w_p = \frac{A(p_w - p_a)(0.089 + 0.0782V)}{Y}F_a\)

Dimensional equation: \(w_p\) in kg/s, \(A\) in m², \(p_w\) and \(p_a\) in kPa, \(V\) in m/s, \(Y\) (latent heat at the water temperature) in kJ/kg.

Variables

Symbol Meaning SI unit
\(A\) Pool surface area m²
\(t_w\) Water temperature K
\(t_a\) Room air temperature K
\(\varphi\) Room relative humidity -
\(V\) Air velocity over the water m/s
\(F_a\) Activity factor -
\(w_p\) Evaporation rate kg/s
\(Q_l\) Latent heat load W
\(V_d\) Water lost per day m³

Method and standards

ASHRAE pool evaporation.

Where it is used

  • Pool hall dehumidifier sizing.
  • Pool water heating energy.

Common mistakes

  • Ignoring activity (splashing raises evaporation).
  • Room air colder than water.

Assumptions and limits

  • Indoor pool; steady state.

References

  • ASHRAE Handbook—HVAC Applications (2019)
  • ch. 6 (natatoriums: w_p = A(p_w − p_a)(0.089 + 0.0782V)/Y × F_a); IAPWS-IF97 for p_w and Y

Questions and answers

Why keep the air warmer than the water?

It lowers the vapour pressure difference and so evaporation, which drives dehumidification and heating energy.

Do pool covers help?

Yes: a cover cuts evaporation almost to zero when the pool is closed.

What do the defaults represent?

A 300 m² hotel pool at 28 °C water and 30 °C, 60 % air.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.