Worked example
Example: Hotel pool 300 m², 28/30 °C, 60 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pool surface area | 300.00 m² |
| Water temperature | 28.000 °C |
| Room air temperature | 30.000 °C |
| Room relative humidity | 60.000 % |
| Air velocity over the water | 0.10000 m/s |
| Activity factor | 0.80000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Evaporation rate | 42.428 kg/h |
| Latent heat load | 28.693 kW |
| Water lost per day | 1,018.3 L |
Open this example in the calculator and change any input.
Formula
\(w_p = \frac{A(p_w - p_a)(0.089 + 0.0782V)}{Y}F_a\)
Dimensional equation: \(w_p\) in kg/s, \(A\) in m², \(p_w\) and \(p_a\) in kPa, \(V\) in m/s, \(Y\) (latent heat at the water temperature) in kJ/kg.
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | Pool surface area | m² |
| \(t_w\) | Water temperature | K |
| \(t_a\) | Room air temperature | K |
| \(\varphi\) | Room relative humidity | - |
| \(V\) | Air velocity over the water | m/s |
| \(F_a\) | Activity factor | - |
| \(w_p\) | Evaporation rate | kg/s |
| \(Q_l\) | Latent heat load | W |
| \(V_d\) | Water lost per day | m³ |
Method and standards
ASHRAE pool evaporation.
Where it is used
- Pool hall dehumidifier sizing.
- Pool water heating energy.
Common mistakes
- Ignoring activity (splashing raises evaporation).
- Room air colder than water.
Assumptions and limits
- Indoor pool; steady state.
References
- ASHRAE Handbook—HVAC Applications (2019)
- ch. 6 (natatoriums: w_p = A(p_w − p_a)(0.089 + 0.0782V)/Y × F_a); IAPWS-IF97 for p_w and Y
Questions and answers
Why keep the air warmer than the water?
It lowers the vapour pressure difference and so evaporation, which drives dehumidification and heating energy.
Do pool covers help?
Yes: a cover cuts evaporation almost to zero when the pool is closed.
What do the defaults represent?
A 300 m² hotel pool at 28 °C water and 30 °C, 60 % air.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.