Cooling Coil Load (Sensible, Latent, Total)

Total, sensible and latent load of an air cooling coil from air flow and the entering and leaving states, with sensible heat ratio and condensate flow.

Air conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: AHU 10 000 m³/h, 27 °C 55 % to 13 °C 92 %Fresh-air unit 5000 m³/h, 35 °C 60 % to 14 °C 95 %Dry coil 3000 m³/h, 30 °C 30 % to 20 °C 52 %

Results

Total coil load80.335kW
Sensible load33.060kW
Latent load47.274kW
Sensible heat ratio41.153%
Condensate66.322kg/h
Dry-air mass flow5,536.8kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: AHU 10 000 m³/h, 27 °C 55 % to 13 °C 92 %. The inputs, in the units selected above:

InputValue
Air flow (at the entering state)10,000 m³/h
Entering dry bulb27.000 °C
Entering relative humidity55.000 %
Leaving dry bulb13.000 °C
Leaving relative humidity92.000 %
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Total coil load76.129 kW
Sensible load45.835 kW
Latent load30.294 kW
Sensible heat ratio60.207 %
Condensate42.748 kg/h
Dry-air mass flow11,533 kg/h

Open this example in the calculator and change any input.

Formula

\(\dot m_{da} = \frac{\dot V}{v_1} \qquad \dot Q_t = \dot m_{da}(h_1 - h_2) \qquad \dot Q_s = \dot m_{da}\,[h(T_1, W_2) - h_2] \qquad \dot Q_l = \dot Q_t - \dot Q_s\)

\(SHR = \frac{\dot Q_s}{\dot Q_t}\ (1\ \text{when}\ \dot Q_t = 0) \qquad \dot m_c = \dot m_{da}\max(W_1 - W_2,\ 0)\)

Variables

Symbol Meaning SI unit
\(\dot V\) air flow at entering state m³/s
\(T_1\) entering dry bulb K
\(\varphi_1\) entering RH –
\(T_2\) leaving dry bulb K
\(\varphi_2\) leaving RH –
\(p\) barometric pressure Pa
\(\dot Q_t\) total load W
\(\dot Q_s\) sensible load W
\(\dot Q_l\) latent load W
\(SHR\) sensible heat ratio –
\(\dot m_c\) condensate kg/s
\(\dot m_{da}\) dry-air flow kg/s
\(h_1, h_2\) entering and leaving enthalpy J/kg
\(W_1, W_2\) humidity ratios kg/kg
\(v_1\) entering specific volume m³/kg

Method and standards

Steady-flow energy and moisture balance on dry air with ASHRAE moist-air enthalpy; the enthalpy of the condensate (about 1 % of the load) is neglected.

Where it is used

  • Sizing AHU and FCU coils.
  • Checking chiller load from field readings.
  • Fresh-air pre-cooling units.

Common mistakes

  • Taking 1.2 kg/m³ for air at every condition.
  • Adding latent heat with the wrong sign.
  • Measuring leaving RH right after the coil where droplets wet the probe.

Assumptions and limits

  • Condensate enthalpy neglected; leaving air at or below saturation.

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics

Questions and answers

What load does an AHU coil take on 10 000 m³/h from 27 °C 55 % to 13 °C 92 %?

76.1 kW total: 45.8 kW sensible and 30.3 kW latent (SHR 0.60), with 42.7 kg/h of condensate.

How is the sensible part split?

It is the enthalpy change at the leaving humidity; the rest, at the entering temperature, is latent.

Which flow do I enter?

The air volume at the entering state; the calculator converts it to dry-air mass.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.