Worked example
Example: AHU 10 000 m³/h, 27 °C 55 % to 13 °C 92 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow (at the entering state) | 10,000 m³/h |
| Entering dry bulb | 27.000 °C |
| Entering relative humidity | 55.000 % |
| Leaving dry bulb | 13.000 °C |
| Leaving relative humidity | 92.000 % |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total coil load | 76.129 kW |
| Sensible load | 45.835 kW |
| Latent load | 30.294 kW |
| Sensible heat ratio | 60.207 % |
| Condensate | 42.748 kg/h |
| Dry-air mass flow | 11,533 kg/h |
Open this example in the calculator and change any input.
Formula
\(\dot m_{da} = \frac{\dot V}{v_1} \qquad \dot Q_t = \dot m_{da}(h_1 - h_2) \qquad \dot Q_s = \dot m_{da}\,[h(T_1, W_2) - h_2] \qquad \dot Q_l = \dot Q_t - \dot Q_s\)
\(SHR = \frac{\dot Q_s}{\dot Q_t}\ (1\ \text{when}\ \dot Q_t = 0) \qquad \dot m_c = \dot m_{da}\max(W_1 - W_2,\ 0)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | air flow at entering state | m³/s |
| \(T_1\) | entering dry bulb | K |
| \(\varphi_1\) | entering RH | – |
| \(T_2\) | leaving dry bulb | K |
| \(\varphi_2\) | leaving RH | – |
| \(p\) | barometric pressure | Pa |
| \(\dot Q_t\) | total load | W |
| \(\dot Q_s\) | sensible load | W |
| \(\dot Q_l\) | latent load | W |
| \(SHR\) | sensible heat ratio | – |
| \(\dot m_c\) | condensate | kg/s |
| \(\dot m_{da}\) | dry-air flow | kg/s |
| \(h_1, h_2\) | entering and leaving enthalpy | J/kg |
| \(W_1, W_2\) | humidity ratios | kg/kg |
| \(v_1\) | entering specific volume | m³/kg |
Method and standards
Steady-flow energy and moisture balance on dry air with ASHRAE moist-air enthalpy; the enthalpy of the condensate (about 1 % of the load) is neglected.
Where it is used
- Sizing AHU and FCU coils.
- Checking chiller load from field readings.
- Fresh-air pre-cooling units.
Common mistakes
- Taking 1.2 kg/m³ for air at every condition.
- Adding latent heat with the wrong sign.
- Measuring leaving RH right after the coil where droplets wet the probe.
Assumptions and limits
- Condensate enthalpy neglected; leaving air at or below saturation.
References
- ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
Questions and answers
What load does an AHU coil take on 10 000 m³/h from 27 °C 55 % to 13 °C 92 %?
76.1 kW total: 45.8 kW sensible and 30.3 kW latent (SHR 0.60), with 42.7 kg/h of condensate.
How is the sensible part split?
It is the enthalpy change at the leaving humidity; the rest, at the entering temperature, is latent.
Which flow do I enter?
The air volume at the entering state; the calculator converts it to dry-air mass.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.