Equal-Area Criterion: Critical Clearing Angle and Time

Critical clearing angle of a generator connected to an infinite bus by the equal-area criterion, and the critical clearing time from the swing equation.

Thermal power plant

Inputs

Examples: Illustrative bolted fault, H = 5 sFault with some transferHeavily loaded, 60 Hz

Accepted: 0.01 to 5
Accepted: 0.05 to 10
Accepted: 0 to 99 %
Accepted: 5 to 100 %
Accepted: 0.5 to 20 s
Accepted: 40 to 70 Hz

Results

During a fault the generator accelerates because it cannot deliver its mechanical power; after clearing it decelerates. It stays in step if the decelerating area under the post-fault power curve, up to δ_max = π − arcsin(P_m/r₂P_max), at least equals the accelerating area. Setting them equal gives the critical clearing angle; integrating the swing equation (2H/ω_s) d²δ/dt² = P_m − r₁P_max sin δ to that angle gives the critical clearing time. For a bolted fault at the terminals (r₁ = 0) this matches t_c = √[4H(δ_c − δ₀)/(ω_s P_m)]. Classical model: no damping, constant voltage behind transient reactance.

Initial rotor angle30.000°
Largest angle after clearing138.19°
Critical clearing angle73.831°
Critical clearing time247.15ms

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative bolted fault, H = 5 s. The inputs, in the units selected above:

InputValue
Mechanical power (pu)0.80000 -
Peak electrical power before the fault (pu)1.8000 -
Peak power during the fault as a share of P_max0 %
Peak power after clearing as a share of P_max80.000 %
Inertia constant5.0000 s
System frequency50.000 Hz

Applying the formula below gives:

ResultValue
Initial rotor angle26.388 °
Largest angle after clearing146.25 °
Critical clearing angle70.686 °
Critical clearing time248.04 ms

Open this example in the calculator and change any input.

Formula

\(\cos\delta_c = \frac{P_m(\delta_{max} - \delta_0) + r_2P_{max}\cos\delta_{max} - r_1P_{max}\cos\delta_0}{(r_2 - r_1)P_{max}}, \quad \frac{2H}{\omega_s}\frac{d^2\delta}{dt^2} = P_m - P_e\)

Variables

Symbol Meaning SI unit
\(P_m\) Mechanical power (pu) -
\(P_{max}\) Peak electrical power before the fault (pu) -
\(r_1\) Peak power during the fault as a share of P_max -
\(r_2\) Peak power after clearing as a share of P_max -
\(H\) Inertia constant s
\(f\) System frequency 1/s
\(\delta_0\) Initial rotor angle rad
\(\delta_{max}\) Largest angle after clearing rad
\(\delta_c\) Critical clearing angle rad
\(t_c\) Critical clearing time s

Method and standards

Equal-area criterion.

Where it is used

  • Checking protection clearing times for generators.
  • Teaching transient stability.

Common mistakes

  • Using the pre-fault power curve after clearing.
  • Mixing H on different MVA bases.

Assumptions and limits

  • Single machine on an infinite bus; classical model; no damping.

References

  • Equal-area criterion and the classical swing equation

Questions and answers

What is the critical clearing time?

The longest a fault may last before the generator loses synchronism; protection must clear faster.

Why does inertia help?

A larger H slows the rotor's acceleration during the fault, so the critical angle is reached later.

What do the defaults represent?

An illustrative generator sending 0.8 pu with 1.8 pu peak transfer, a bolted fault, 0.8 of the transfer after clearing, H = 5 s, 50 Hz.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kundur, Power System Stability and Control (McGraw-Hill, 1994), Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.