FireCADCalc

Electricity Bill: Demand Charge, Energy Charge and Load Factor

Monthly HT electricity bill from recorded maximum demand, contract demand with a minimum billing share, demand and energy rates, with load factor and cost per kWh.

Inputs

Examples: Illustrative factory monthLow load month, minimum billingDemand above contract

Accepted: 0 to 277,780,000 kWh
Accepted: 0.001 to 1,000,000 kVA
Accepted: 0.001 to 1,000,000 kVA
Accepted: 0 to 100 %
Accepted: 0 to 100,000
Accepted: 0 to 1,000
Accepted: 1 to 744 h

Results

Two-part tariffs charge for energy (kWh) and for the highest demand recorded in any demand interval (usually 15 or 30 minutes), billed at no less than a set share of the contract demand. A low load factor (energy over maximum demand × hours) spreads the demand charge over fewer kWh, raising the average cost. Shaving peaks, staggering motor starts and improving power factor (on kVA billing) cut the demand charge. Taxes, power-factor and time-of-day adjustments and excess-demand penalties vary by tariff and are not included.

Billing demand1,150.0kVA
Demand charge517,500
Energy charge3,900,000
Demand plus energy charge4,417,500
Average cost per kWh7.3625
Load factor (kWh over MD × hours)70.126%
Demand above contract150.00kVA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative factory month. The inputs, in the units selected above:

InputValue
Energy used in the month150,000 kWh
Recorded maximum demand400.00 kVA
Contract demand500.00 kVA
Minimum billing demand as a share of contract demand75.000 %
Demand rate per kVA per month400.00 -
Energy rate per kWh7.0000 -
Hours in the billing month720.00 h

Applying the formula below gives:

ResultValue
Billing demand400.00 kVA
Demand charge160,000
Energy charge1,050,000
Demand plus energy charge1,210,000
Average cost per kWh8.0667
Load factor (kWh over MD × hours)52.083 %
Demand above contract0 kVA

Open this example in the calculator and change any input.

Formula

\(BD = \max(MD,\ f_m CD), \quad C = r_d BD + r_e E, \quad LF = \frac{E}{MD\cdot t}\)

Variables

Symbol Meaning SI unit
\(E\) Energy used in the month J
\(MD\) Recorded maximum demand VA
\(CD\) Contract demand VA
\(f_m\) Minimum billing demand as a share of contract demand -
\(r_d\) Demand rate per kVA per month -
\(r_e\) Energy rate per kWh -
\(t\) Hours in the billing month s
\(BD\) Billing demand VA
\(C_d\) Demand charge -
\(C_e\) Energy charge -
\(C\) Demand plus energy charge -
\(c\) Average cost per kWh -
\(LF\) Load factor (kWh over MD × hours) -
\(\Delta S\) Demand above contract VA

Method and standards

Electricity bill.

Where it is used

  • Industrial and commercial HT consumers.
  • Deciding on contract demand changes.

Common mistakes

  • Comparing load factors on kW and kVA.
  • Ignoring the minimum billing demand when reducing load.

Assumptions and limits

  • Simple two-part tariff; no taxes or rebates.

References

  • Two-part tariff arithmetic

Questions and answers

What is billing demand?

The higher of the recorded maximum demand and the minimum share (often 75–85 %) of contract demand.

How does load factor affect cost per unit?

At the defaults the load factor is 52 % and the average cost is about 8.07 per kWh against an energy rate of 7.

What do the defaults represent?

An illustrative factory using 150,000 kWh a month with 400 kVA maximum demand on a 500 kVA contract, 75 % minimum billing, demand rate 400 per kVA and energy rate 7 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.