Combined Power Factor and Current of Several Loads

Total real, reactive and apparent power, overall power factor and line current of up to four loads with different power factors, lagging or leading.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative three loads at 415 VWith a leading loadFour motors at 6.6 kV

Accepted: 100 to 800,000 V
Accepted: 0 to 1,000,000 kW
Accepted: -1 to 1
Accepted: 0 to 1,000,000 kW
Accepted: -1 to 1
Accepted: 0 to 1,000,000 kW
Accepted: -1 to 1
Accepted: 0 to 1,000,000 kW
Accepted: -1 to 1

Results

Add real and reactive powers separately (Q = P·tan φ, negative for leading loads); never average power factors. The overall power factor is P/S.

Total real power125.00kW
Total reactive power (+ lagging)79.457kvar
Total apparent power148.12kVA
Overall power factor0.84393
Line current206.06A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative three loads at 415 V. The inputs, in the units selected above:

InputValue
Line-to-line voltage415.00 V
Load 1 power50.000 kW
Load 1 power factor (negative = leading)0.80000 -
Load 2 power30.000 kW
Load 2 power factor0.90000 -
Load 3 power20.000 kW
Load 3 power factor1.0000 -
Load 4 power0 kW
Load 4 power factor0.85000 -

Applying the formula below gives:

ResultValue
Total real power100.00 kW
Total reactive power (+ lagging)52.030 kvar
Total apparent power112.73 kVA
Overall power factor0.88711
Line current156.82 A

Open this example in the calculator and change any input.

Formula

\(P = \sum P_k, \quad Q = \sum P_k\tan\varphi_k, \quad pf = \frac{P}{\sqrt{P^2 + Q^2}}\)

Variables

Symbol Meaning SI unit
\(V\) Line-to-line voltage V
\(P_1\) Load 1 power W
\(pf_1\) Load 1 power factor (negative = leading) -
\(P_2\) Load 2 power W
\(pf_2\) Load 2 power factor -
\(P_3\) Load 3 power W
\(pf_3\) Load 3 power factor -
\(P_4\) Load 4 power W
\(pf_4\) Load 4 power factor -
\(P\) Total real power W
\(Q\) Total reactive power (+ lagging) var
\(S\) Total apparent power VA
\(pf\) Overall power factor -
\(I\) Line current A

Method and standards

Power summation.

Where it is used

  • Board and transformer loading.
  • Power factor correction studies.

Common mistakes

  • Averaging power factors.
  • Forgetting the sign of leading loads.

Assumptions and limits

  • Balanced three-phase loads at one voltage.

References

  • Power triangle summation

Questions and answers

Can I average the power factors?

No: power factors combine through reactive power, weighted by each load's kW; a simple average is wrong.

What does a leading load do?

Its negative reactive power offsets lagging loads, as a capacitor bank does.

What do the defaults represent?

An illustrative 415 V board with 50 kW at 0.8, 30 kW at 0.9 and 20 kW resistive load.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.