FireCADCalc

Wound-Rotor Motor: External Resistance for Maximum Starting Torque

Thevenin equivalent, slip at maximum torque, pull-out torque and the external rotor resistance that gives maximum torque at standstill for a wound-rotor motor.

Inputs

Examples: Illustrative 460 V 4-pole machine415 V 6-pole, 50 Hz3.3 kV mill motor

Accepted: 100 to 15,000 V
Accepted: 10 to 400 Hz
Accepted: 2 to 48
Accepted: 0.0001 to 100 Ω
Accepted: 0.0001 to 100 Ω
Accepted: 1 to 10,000 Ω
Accepted: 0.0001 to 100 Ω
Accepted: 0.0001 to 100 Ω
Accepted: 0.1 to 20

Results

Thevenin of the stator and magnetising branch: V_TH = V_φX_M/√(R₁² + (X₁ + X_M)²), Z_TH = jX_M(R₁ + jX₁)/(R₁ + j(X₁ + X_M)). Maximum torque occurs at s_max = R₂′/√(R_TH² + (X_TH + X₂′)²) and its value does not depend on rotor resistance. Adding R_ext′ = √(R_TH² + (X_TH + X₂′)²) − R₂′ puts maximum torque at standstill; on the rotor side it is divided by a². The resistor is cut out in steps as the motor speeds up.

Thevenin voltage per phase1,867.9V
Slip at maximum torque (no external R)7.3034%
Pull-out torque10,032N·m
Starting torque without external R1,553.7N·m
External resistance referred to stator5.7115Ω
External resistance per rotor phase2.5385Ω

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 460 V 4-pole machine. The inputs, in the units selected above:

InputValue
Line voltage (star)460.00 V
Frequency60.000 Hz
Number of poles4.0000 -
Stator resistance per phase0.64100 Ω
Stator leakage reactance1.1060 Ω
Magnetising reactance26.300 Ω
Rotor resistance referred to stator0.33200 Ω
Rotor leakage reactance referred0.46400 Ω
Stator-to-rotor turns ratio2.0000 -

Applying the formula below gives:

ResultValue
Thevenin voltage per phase254.79 V
Slip at maximum torque (no external R)20.141 %
Pull-out torque230.80 N·m
Starting torque without external R106.56 N·m
External resistance referred to stator1.3164 Ω
External resistance per rotor phase0.32909 Ω

Open this example in the calculator and change any input.

Formula

\(s_{max} = \frac{R_2'}{\sqrt{R_{TH}^2 + (X_{TH} + X_2')^2}}, \quad T_{max} = \frac{3V_{TH}^2}{2\omega_s\left[R_{TH} + \sqrt{R_{TH}^2 + (X_{TH} + X_2')^2}\right]}, \quad R_{ext}' = \sqrt{R_{TH}^2 + (X_{TH} + X_2')^2} - R_2'\)

Variables

Symbol Meaning SI unit
\(V_L\) Line voltage (star) V
\(f\) Frequency 1/s
\(p\) Number of poles -
\(R_1\) Stator resistance per phase Ω
\(X_1\) Stator leakage reactance Ω
\(X_M\) Magnetising reactance Ω
\(R_2'\) Rotor resistance referred to stator Ω
\(X_2'\) Rotor leakage reactance referred Ω
\(a\) Stator-to-rotor turns ratio -
\(V_{TH}\) Thevenin voltage per phase V
\(s_{max}\) Slip at maximum torque (no external R) -
\(T_{max}\) Pull-out torque N·m
\(T_{start}\) Starting torque without external R N·m
\(R_{ext}'\) External resistance referred to stator Ω
\(R_{ext}\) External resistance per rotor phase Ω

Method and standards

Rotor resistance.

Where it is used

  • Slip-ring motor starter design.
  • Teaching torque-speed curves.

Common mistakes

  • Forgetting to refer resistance through the turns ratio.
  • Using line instead of phase voltage.

Assumptions and limits

  • Steady-state equivalent circuit; constant parameters; star connection.

References

  • Thevenin equivalent circuit of the induction motor

Questions and answers

Why does rotor resistance not change the maximum torque?

It only shifts the slip at which the maximum occurs; the peak depends on the stator and leakage reactances.

Why use a wound-rotor motor today?

For very heavy, high-inertia starts on weak supplies (mills, crushers), though VFDs have replaced many.

What do the defaults represent?

An illustrative 460 V, 60 Hz, 4-pole machine with the equivalent circuit R₁ 0.641, X₁ 1.106, X_M 26.3, R₂′ 0.332, X₂′ 0.464 Ω and turns ratio 2.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.