Worked example
Example: Illustrative 110 kW pump motor at 3.5 x. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Motor rated torque | 715.00 N·m |
| Locked-rotor current ratio | 6.5000 - |
| Locked-rotor torque ratio | 2.2000 - |
| Current limit setting | 3.5000 - |
| Average load torque during start | 35.000 % |
| Total moment of inertia | 25.000 kg·m² |
| Full speed | 1,480.0 rpm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Motor voltage at the current limit | 53.846 % |
| Motor torque at the limit | 456.08 N·m |
| Accelerating torque | 205.83 N·m |
| Start time | 18.825 s |
| Lowest current limit that starts the load | 2.5926 |
Open this example in the calculator and change any input.
Formula
\(\frac{U}{U_n} = \frac{k}{I_{LR}/I_n}, \quad T_m = T_{LR}\left(\frac U{U_n}\right)^2, \quad t_{st} = \frac{J\omega}{T_m - T_L}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_n\) | Motor rated torque | N·m |
| \(I_{LR}/I_n\) | Locked-rotor current ratio | - |
| \(T_{LR}/T_n\) | Locked-rotor torque ratio | - |
| \(I_{lim}/I_n\) | Current limit setting | - |
| \(T_L/T_n\) | Average load torque during start | - |
| \(J\) | Total moment of inertia | kg·m² |
| \(n\) | Full speed | rad/s |
| \(U/U_n\) | Motor voltage at the current limit | - |
| \(T_m\) | Motor torque at the limit | N·m |
| \(T_a\) | Accelerating torque | N·m |
| \(t_{st}\) | Start time | s |
| \((I_{lim}/I_n)_{min}\) | Lowest current limit that starts the load | - |
Method and standards
Soft starting.
Where it is used
- Setting soft starters for pumps and fans.
- Checking whether a load can be soft-started.
Common mistakes
- Expecting full torque at reduced current.
- Ignoring starts-per-hour limits.
Assumptions and limits
- Constant motor torque during run-up; average load torque.
References
- Reduced-voltage torque scaling (T ∝ U², I ∝ U)
Questions and answers
Can a soft starter start any load?
No: torque falls with the square of voltage, so heavy loads like crushers or loaded conveyors may need a VFD.
Why does a lower current limit lengthen the start?
Torque falls with the square of current, leaving less accelerating torque.
What do the defaults represent?
An illustrative 110 kW, 1,480 rpm motor (715 N·m) with 6.5× locked-rotor current and 2.2× torque, a 3.5× current limit, a 35 % load and 25 kg·m² inertia.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Hughes and Drury, Electric Motors and Drives, 5th ed. (Newnes, 2019), Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)