Self-Excited Induction Generator Capacitance

Capacitance per phase for a self-excited induction generator in delta or star from its magnetising current and the reactive power of the load.

Inputs

Examples: Illustrative 415 V 15 kW loadMicro-hydro 5 kW resistive load60 Hz 480 V 50 kW motor load

Accepted: 100 to 15,000 V
Accepted: 10 to 400 Hz
Accepted: 0.1 to 5,000 A
Accepted: 0 to 10,000 kW
Accepted: 30 to 100 %
Accepted: 1 to 2

Results

An induction machine driven above synchronous speed generates only if something supplies its magnetising current. Capacitors must supply Q_m = √3V_LI₀ plus the load's reactive power. Per phase: delta C = Q/(3ωV_L²); star C = Q/(ωV_L²), three times larger for the same kvar. The machine self-excites only with enough residual magnetism and capacitance; voltage and frequency drift with load and speed unless regulated.

Magnetising reactive power3.5940kvar
Load reactive power0kvar
Capacitance per phase, delta25.463µF
Capacitance per phase, star76.389µF

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 415 V 15 kW load. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
Frequency50.000 Hz
No-load (magnetising) current12.000 A
Load real power15.000 kW
Load power factor (lagging)90.000 %
Margin on capacitance1.1000 -

Applying the formula below gives:

ResultValue
Magnetising reactive power8.6256 kvar
Load reactive power7.2648 kvar
Capacitance per phase, delta107.69 µF
Capacitance per phase, star323.06 µF

Open this example in the calculator and change any input.

Formula

\(Q = k\left(\sqrt3V_LI_0 + P_L\tan\varphi_L\right), \quad C_\Delta = \frac{Q}{3\omega V_L^2}, \quad C_Y = 3C_\Delta\)

Variables

Symbol Meaning SI unit
\(V_L\) Line voltage V
\(f\) Frequency 1/s
\(I_0\) No-load (magnetising) current A
\(P_L\) Load real power W
\(\cos\varphi_L\) Load power factor (lagging) -
\(k\) Margin on capacitance -
\(Q_m\) Magnetising reactive power var
\(Q_L\) Load reactive power var
\(C_\Delta\) Capacitance per phase, delta F
\(C_Y\) Capacitance per phase, star F

Method and standards

Self-excitation.

Where it is used

  • Micro-hydro and small wind induction generators.
  • Standby conversions of motors to generators.

Common mistakes

  • Using the star formula for a delta bank.
  • Ignoring the load's reactive power.

Assumptions and limits

  • Rated voltage and frequency; magnetising current at rated voltage.

References

  • Reactive power balance of the self-excited induction generator

Questions and answers

Why does an induction generator need capacitors off-grid?

It cannot make its own magnetising current; on the grid the network supplies it, off-grid capacitors must.

Why does voltage collapse with heavy inductive load?

The load takes reactive power the capacitors were supplying to the machine, so excitation falls.

What do the defaults represent?

An illustrative 415 V, 50 Hz machine with 12 A no-load current feeding 15 kW at 0.9 power factor, with a 10 % margin.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.