Worked example
Example: Illustrative 37 kW 4-pole at 1000 rpm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated output | 37.000 kW |
| Supply frequency | 50.000 Hz |
| Number of poles | 4.0000 - |
| Rated speed | 1,475.0 rpm |
| Breakdown torque / rated torque | 2.6000 - |
| Speed of interest | 1,000.0 rpm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Synchronous speed | 1,500.0 rpm |
| Rated slip | 1.6667 % |
| Rated torque | 239.54 N·m |
| Breakdown slip | 8.3333 % |
| Breakdown speed | 1,375.0 rpm |
| Torque at the speed of interest | 293.09 N·m |
| Starting torque by Kloss (s = 1) | 103.09 N·m |
Open this example in the calculator and change any input.
Formula
\(T = \frac{2T_k}{s/s_k + s_k/s}, \quad s_k = s_n\left(\lambda + \sqrt{\lambda^2 - 1}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Rated output | W |
| \(f\) | Supply frequency | 1/s |
| \(p\) | Number of poles | - |
| \(n_r\) | Rated speed | 1/s |
| \(\lambda\) | Breakdown torque / rated torque | - |
| \(n\) | Speed of interest | 1/s |
| \(n_s\) | Synchronous speed | 1/s |
| \(s_n\) | Rated slip | - |
| \(T_n\) | Rated torque | N·m |
| \(s_k\) | Breakdown slip | - |
| \(n_k\) | Breakdown speed | 1/s |
| \(T\) | Torque at the speed of interest | N·m |
| \(T_{st}\) | Starting torque by Kloss (s = 1) | N·m |
Method and standards
Kloss formula.
Where it is used
- Load acceleration and stall checks.
- Variable-load drives.
Common mistakes
- Using Kloss for starting torque of deep-bar rotors.
- Using an odd pole number.
Assumptions and limits
- Constant voltage and frequency; stator resistance neglected.
References
- Kloss approximation of the induction motor torque curve
Questions and answers
What is breakdown torque?
The maximum torque the motor can develop; loading beyond it stalls the motor. Standard motors reach about 2–3 times rated torque.
Why does the Kloss starting torque look low?
Rotor resistance rises at standstill in deep-bar rotors, raising starting torque well above the simple curve.
What do the defaults represent?
An illustrative 37 kW, 4-pole, 50 Hz motor running at 1,475 rpm with breakdown torque 2.6 times rated, checked at 1,000 rpm.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 4th ed. (McGraw-Hill, 2005), ch. 7