Worked example
Example: Conductivity: feed 150, boiler water 3000 µS/cm, 10 t/h steam. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Feedwater reading (conductivity, chloride or silica) | 150.00 - |
| Boiler water reading (same parameter and unit) | 3,000.0 - |
| Steam flow (for the blowdown flow) | 10,000 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Blowdown, share of steam | 5.2632 % |
| Blowdown, share of feedwater | 5.0000 % |
| Cycles of concentration | 20.000 |
| Blowdown flow | 526.32 kg/h |
Open this example in the calculator and change any input.
Formula
\(N = \frac{B}{f} \qquad b_{fw} = \frac{f}{B} \qquad b_s = \frac{f}{B - f} \qquad \dot m_{bd} = b_s\,\dot m_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f\) | feedwater reading | any (same for both) |
| \(B\) | boiler water reading | any (same for both) |
| \(\dot m_s\) | steam flow | kg/s |
| \(N\) | cycles of concentration | – |
| \(b_{fw}\) | blowdown, share of feedwater | – |
| \(b_s\) | blowdown, share of steam | – |
| \(\dot m_{bd}\) | blowdown flow | kg/s |
Method and standards
Steady mass balance of a substance that the steam does not carry: what enters with the feedwater leaves with the blowdown.
Where it is used
- Checking blowdown against the water treatment programme.
- Valuing automatic TDS control.
- Water and fuel loss estimates.
Common mistakes
- Using make-up water instead of the feedwater after condensate mixing.
- Comparing conductivity of samples at different temperatures without compensation.
- Using silica at high pressure, where steam carries some.
Assumptions and limits
- Steady operation; the parameter is conserved and not carried by steam.
- Conductivity is read as measured (unneutralised); hydroxide and phosphate dosing raise boiler water conductivity, so the cycles come out high. Silica is carried by steam at high pressure. Chloride is the safest reading.
References
- Dissolved-solids mass balance of the boiler drum
Questions and answers
How do I find the actual blowdown rate?
From the ratio of a conserved reading in boiler water and feedwater. Feedwater at 150 µS/cm and boiler water at 3000 µS/cm is 20 cycles: blowdown is 5 % of feedwater or 5.26 % of steam, 526 kg/h on a 10 t/h boiler.
Which reading should I use?
Chloride is best because it stays dissolved and nothing is dosed with it. Conductivity is easiest but changes with chemical dosing; silica can be carried by steam at high pressure.
Why is this better than reading the blowdown valve?
Valve openings and flow estimates are poor; the water analysis measures what actually leaves.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.