Boiler Blowdown Rate from Water Analysis

Actual boiler blowdown rate and cycles of concentration from feedwater and boiler water readings of conductivity, chloride or silica, with the blowdown flow.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserBoilerWater treatment plant

Inputs

Examples: Conductivity: feed 150, boiler water 3000 µS/cm, 10 t/h steamChloride: feed 12, boiler 240 mg/L, 25 t/hSilica: feed 0.5, boiler 15 mg/L, 60 t/h

Any conserved quantity that steam does not carry: use the same unit for both readings.

Results

Blowdown, share of steam5.2632%
Blowdown, share of feedwater5.0000%
Cycles of concentration20.000
Blowdown flow1,315.8kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Conductivity: feed 150, boiler water 3000 µS/cm, 10 t/h steam. The inputs, in the units selected above:

InputValue
Feedwater reading (conductivity, chloride or silica)150.00 -
Boiler water reading (same parameter and unit)3,000.0 -
Steam flow (for the blowdown flow)10,000 kg/h

Applying the formula below gives:

ResultValue
Blowdown, share of steam5.2632 %
Blowdown, share of feedwater5.0000 %
Cycles of concentration20.000
Blowdown flow526.32 kg/h

Open this example in the calculator and change any input.

Formula

\(N = \frac{B}{f} \qquad b_{fw} = \frac{f}{B} \qquad b_s = \frac{f}{B - f} \qquad \dot m_{bd} = b_s\,\dot m_s\)

Variables

Symbol Meaning SI unit
\(f\) feedwater reading any (same for both)
\(B\) boiler water reading any (same for both)
\(\dot m_s\) steam flow kg/s
\(N\) cycles of concentration –
\(b_{fw}\) blowdown, share of feedwater –
\(b_s\) blowdown, share of steam –
\(\dot m_{bd}\) blowdown flow kg/s

Method and standards

Steady mass balance of a substance that the steam does not carry: what enters with the feedwater leaves with the blowdown.

Where it is used

  • Checking blowdown against the water treatment programme.
  • Valuing automatic TDS control.
  • Water and fuel loss estimates.

Common mistakes

  • Using make-up water instead of the feedwater after condensate mixing.
  • Comparing conductivity of samples at different temperatures without compensation.
  • Using silica at high pressure, where steam carries some.

Assumptions and limits

  • Steady operation; the parameter is conserved and not carried by steam.
  • Conductivity is read as measured (unneutralised); hydroxide and phosphate dosing raise boiler water conductivity, so the cycles come out high. Silica is carried by steam at high pressure. Chloride is the safest reading.

References

  • Dissolved-solids mass balance of the boiler drum

Questions and answers

How do I find the actual blowdown rate?

From the ratio of a conserved reading in boiler water and feedwater. Feedwater at 150 µS/cm and boiler water at 3000 µS/cm is 20 cycles: blowdown is 5 % of feedwater or 5.26 % of steam, 526 kg/h on a 10 t/h boiler.

Which reading should I use?

Chloride is best because it stays dissolved and nothing is dosed with it. Conductivity is easiest but changes with chemical dosing; silica can be carried by steam at high pressure.

Why is this better than reading the blowdown valve?

Valve openings and flow estimates are poor; the water analysis measures what actually leaves.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.