Steam Tracing Heat Loss and Steam Consumption

Heat lost from an insulated steam-traced pipe held at a set temperature in cold weather (ISO 12241), and the tracer steam needed to replace it.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)ISO 12241 (thermal insulation)Fuel oil and gas system

Inputs

Examples: DN100 (114.3 mm) held at 60 °C, -5 °C ambient, 50 mm wool, 200 m, 4.5 bar(a)Fuel oil DN80 (88.9 mm) at 90 °C, 10 °C, 40 mm, 150 m, 7 bar(a)DN50 (60.3 mm) frost protection 10 °C, -20 °C, 25 mm, 100 m, 2.5 bar(a)

Results

Loss of the pipe alone under its insulation; tracer runs add a little, and runs longer than about 50 m need their own trap.

Heat loss per metre29.493W/m
Heat loss of the traced length4.4240kW
Tracer steam needed7.7102kg/h
Tracer steam temperature164.95°C
Cladding surface temperature23.054°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: DN100 (114.3 mm) held at 60 °C, -5 °C ambient, 50 mm wool, 200 m, 4.5 bar(a). The inputs, in the units selected above:

InputValue
Traced pipe outer diameter114.30 mm
Insulation thickness50.000 mm
Insulation thermal conductivity0.045000 W/(m·K)
Temperature to maintain60.000 °C
Lowest design ambient temperature-5.0000 °C
Emissivity of the cladding0.10000 -
Traced length200.00 m
Tracer steam pressure (absolute, saturated)4.5000 bar

Applying the formula below gives:

ResultValue
Heat loss per metre24.788 W/m
Heat loss of the traced length4.9576 kW
Tracer steam needed8.4178 kg/h
Tracer steam temperature147.91 °C
Cladding surface temperature4.8958 °C

Open this example in the calculator and change any input.

Formula

\(q' = \frac{T_i - T_{sf}}{\ln(D/D_o)/(2\pi\lambda)} = h_{se}\,\pi D\,(T_{sf} - T_a) \qquad \dot Q = q' L \qquad \dot m_s = \frac{\dot Q}{h_{fg}(p_s)}\)

\(h_{se} = h_{cv} + h_r, \quad h_{cv} = 1.25\left(\frac{\Delta T}{D}\right)^{1/4}\ (D^3\Delta T \le 10\ \mathrm{m^3K}),\quad h_{cv} = 1.21\,\Delta T^{1/3}\ (D^3\Delta T > 10), \quad h_r = \varepsilon\sigma\frac{T_{sf}^4 - T_a^4}{T_{sf} - T_a}\)

Variables

Symbol Meaning SI unit
\(D_o\) pipe outer diameter m
\(t\) insulation thickness m
\(\lambda\) insulation conductivity W/(m·K)
\(T_i\) temperature to maintain K
\(T_a\) design ambient K
\(\varepsilon\) cladding emissivity –
\(L\) traced length m
\(p_s\) tracer steam pressure Pa
\(q'\) loss per metre W/m
\(\dot Q\) total loss W
\(\dot m_s\) tracer steam kg/s
\(T_s\) tracer steam temperature K
\(T_{sf}\) cladding surface temperature K
\(D\) outer diameter of insulation m
\(h_{se}\) ISO 12241 surface coefficient W/(m²·K)
\(h_{fg}\) latent heat J/kg
\(h_{cv}\), \(h_r\) convection and radiation parts of \(h_{se}\) W/(m²·K)
\(\Delta T\) surface to ambient temperature difference K
\(\sigma\) Stefan–Boltzmann constant W/(m²·K⁴)

Method and standards

ISO 12241 insulated pipe loss in still air at the lowest design ambient; tracer steam condenses fully, IAPWS-IF97 latent heat.

Where it is used

  • Fuel oil and viscous product lines.
  • Instrument impulse lines.
  • Frost protection of water lines.

Common mistakes

  • Using normal rather than winter ambient.
  • Wet or damaged insulation.
  • Ignoring wind, which raises losses.

Assumptions and limits

  • Still air (wind ignored); insulation dry; tracer contact and the extra area of the tracer are ignored.
  • A tracer less than 10 K hotter than the pipe is flagged; the result is still shown for the heat loss.
  • The temperature to maintain must be above the ambient temperature.

References

  • ISO 12241
  • IAPWS-IF97

Questions and answers

How much steam traces 200 m of DN100 held at 60 °C in −5 °C weather?

With 50 mm wool and aluminium cladding: 24.8 W/m, 4.96 kW in all, 8.4 kg/h of 4.5 bar(a) steam.

How hot must the tracer be?

Well above the holding temperature; here 147.9 °C against 60 °C.

Why limit tracer run length?

Long runs back up condensate; practice is a trap every 30–50 m.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.