Worked example
Example: Illustrative 1 MW loop, 5 m, 7 MPa, 247 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat input | 1,000.0 kW |
| Elevation of cooler thermal centre above heater thermal centre | 5.0000 m |
| Reference flow area | 100.00 cm² |
| Total loss coefficient referred to that area | 20.000 - |
| Loop pressure | 7.0000 MPa |
| Mean loop temperature | 246.85 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Natural circulation flow | 4.9811 kg/s |
| Temperature rise across the heater | 41.892 K |
| Velocity at the reference area | 0.61713 m/s |
| Volumetric expansion coefficient | 1,854.1 µm/(m·K) |
| Density at the mean temperature | 807.13 kg/m³ |
| Specific heat | 4.7923 kJ/(kg·K) |
Open this example in the calculator and change any input.
Formula
\(\dot m = \left(\frac{2\rho^2A^2\beta g\Delta zQ}{c_p\Sigma K}\right)^{1/3}, \quad \Delta T = \frac{Q}{\dot mc_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Heat input | W |
| \(\Delta z\) | Elevation of cooler thermal centre above heater thermal centre | m |
| \(A\) | Reference flow area | m² |
| \(\Sigma K\) | Total loss coefficient referred to that area | - |
| \(p\) | Loop pressure | Pa |
| \(\bar T\) | Mean loop temperature | K |
| \(\dot m\) | Natural circulation flow | kg/s |
| \(\Delta T\) | Temperature rise across the heater | K |
| \(v\) | Velocity at the reference area | m/s |
| \(\beta\) | Volumetric expansion coefficient | 1/K |
| \(\rho\) | Density at the mean temperature | kg/m³ |
| \(c_p\) | Specific heat | J/(kg·K) |
Method and standards
Natural circulation momentum and energy balance.
Where it is used
- Decay heat removal and passive safety systems.
- Solar thermosiphons and transformer cooling loops.
Common mistakes
- Taking Δz between the vessels instead of between the thermal centres.
- Mixing loss coefficients referred to different areas.
Assumptions and limits
- Single phase; steady; Boussinesq; friction as form losses.
References
- Steady single-phase natural circulation (Boussinesq loop balance)
Questions and answers
Why does flow vary with the cube root of power?
Doubling the heat raises the buoyancy, but friction rises with the square of the flow; together ṁ ∝ Q^(1/3).
How do designers increase natural circulation?
Raise the cooler above the core (larger Δz) and cut the loop resistance; passive plants use tall chimneys.
What do the defaults represent?
An illustrative 1 MW decay-heat loop: 5 m between thermal centres, 0.01 m² reference area, ΣK = 20, water at 7 MPa and 247 °C mean.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Todreas and Kazimi, Nuclear Systems I: Thermal Hydraulic Fundamentals (Hemisphere, 1990), ch. 9