Worked example
Example: Illustrative 3000 MWt, 1 year, 1 h to 1 day. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Operating thermal power before shutdown | 3,000.0 MW |
| Operating time at that power | 365.25 d |
| Time after shutdown | 1.0000 h |
| Later time (for energy released from t to t₂) | 24.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Decay heat fraction at t | 1.0125 % |
| Decay heat power at t | 30.376 MW |
| Decay heat fraction at t₂ | 0.44379 % |
| Decay energy released between t and t₂ | 1,423.2 GJ |
| Average decay power between t and t₂ | 17.188 MW |
Open this example in the calculator and change any input.
Formula
\(\frac{P}{P_0} = 0.0622\left[t^{-0.2} - (t + T_0)^{-0.2}\right], \quad E = 0.0622P_0\left[\frac{t^{0.8} - (t + T_0)^{0.8}}{0.8}\right]_{t}^{t_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_0\) | Operating thermal power before shutdown | W |
| \(T_0\) | Operating time at that power | s |
| \(t\) | Time after shutdown | s |
| \(t_2\) | Later time (for energy released from t to t₂) | s |
| \(P/P_0\) | Decay heat fraction at t | - |
| \(P(t)\) | Decay heat power at t | W |
| \(P(t_2)/P_0\) | Decay heat fraction at t₂ | - |
| \(E\) | Decay energy released between t and t₂ | J |
| \(\bar P\) | Average decay power between t and t₂ | W |
Method and standards
Way–Wigner decay-heat estimate.
Where it is used
- Shutdown cooling, spent fuel pool and cask heat estimates.
- Emergency cooling and station blackout studies (screening).
Common mistakes
- Using it for licensing (use the ANS-5.1 standard).
- Entering times in hours where the formula needs seconds (the calculator converts).
Assumptions and limits
- Fission products only; actinide decay heat (U-239, Np-239) is not included.
References
- Way–Wigner approximation for fission-product decay heat
Questions and answers
How large is decay heat?
About 6–7 % of full power just after shutdown, about 1 % after an hour and 0.4–0.5 % after a day: still megawatts for a large reactor.
Why does it matter so much?
Cooling must continue after shutdown; loss of it melted the cores at Three Mile Island and Fukushima.
What do the defaults represent?
An illustrative 3,000 MW thermal reactor after a year at power, one hour after shutdown, with the energy released up to one day.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Lamarsh and Baratta, Introduction to Nuclear Engineering, 3rd ed. (Prentice Hall, 2001), ch. 8, El-Wakil, Powerplant Technology (McGraw-Hill, 1984), ch. 9-11