Strainer Pressure Drop when Clean and Clogged

Pressure drop across a pipeline strainer from its loss coefficient and flow, its rise as the screen clogs, and the clogging at which a differential alarm is reached.

Thermal power plantProcess steam and utilitiesRefinery and petrochemical

Inputs

Examples: Illustrative 6-inch strainer, half blockedPump suction 4-inch, 30 % blockedOil 8-inch basket

Accepted: 0.036 to 36,000 m³/h
Accepted: 10 to 2,000 mm
Accepted: 0.1 to 50
Accepted: 1 to 2,000 kg/m³
Accepted: 0 to 95 %
Accepted: 0.1 to 1,000 kPa

Results

Δp = Kρv²/2 clean; the screen loss scales with 1/(open area)², so with a fraction c blocked Δp ≈ Δp₀/(1 − c)² (housing losses assumed small). Set the alarm well below the screen's collapse rating.

Pipe velocity1.5719m/s
Clean pressure drop3.0886kPa
Pressure drop at that clogging12.354kPa
Clogging at the alarm75.146%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 6-inch strainer, half blocked. The inputs, in the units selected above:

InputValue
Flow100.00 m³/h
Pipe (inlet) diameter150.00 mm
Clean strainer loss coefficient2.5000 -
Fluid density1,000.0 kg/m³
Fraction of screen open area blocked50.000 %
Differential pressure alarm50.000 kPa

Applying the formula below gives:

ResultValue
Pipe velocity1.5719 m/s
Clean pressure drop3.0886 kPa
Pressure drop at that clogging12.354 kPa
Clogging at the alarm75.146 %

Open this example in the calculator and change any input.

Formula

\(\Delta p_0 = K\frac{\rho v^2}{2}, \quad \Delta p_c = \frac{\Delta p_0}{(1 - c)^2}, \quad c_{al} = 1 - \sqrt{\frac{\Delta p_0}{\Delta p_{al}}}\)

Variables

Symbol Meaning SI unit
\(Q\) Flow m³/s
\(D\) Pipe (inlet) diameter m
\(K\) Clean strainer loss coefficient -
\(\rho\) Fluid density kg/m³
\(c\) Fraction of screen open area blocked -
\(\Delta p_{al}\) Differential pressure alarm Pa
\(v\) Pipe velocity m/s
\(\Delta p_0\) Clean pressure drop Pa
\(\Delta p_c\) Pressure drop at that clogging Pa
\(c_{al}\) Clogging at the alarm -

Method and standards

Strainer loss.

Where it is used

  • Strainer selection and alarm setting.
  • Pump suction protection.

Common mistakes

  • Taking the clean drop as the design drop.
  • Ignoring suction NPSH with clogging.

Assumptions and limits

  • Screen loss dominates; incompressible flow.

References

  • Loss coefficient with open-area scaling
  • Crane Technical Paper 410
  • Flow of Fluids through Valves
  • Fittings and Pipe (Crane)

Questions and answers

Why does pressure drop rise so fast near full clogging?

Velocity through the remaining open area rises as the blockage grows and loss goes with velocity squared: 50 % blocked gives four times the clean drop.

Where are pump suction strainers a problem?

A clogging suction strainer eats into NPSH margin and can make the pump cavitate.

What do the defaults represent?

An illustrative 6-inch strainer (K = 2.5) passing 100 m³/h of water, half blocked, with a 0.5 bar alarm.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.