Worked example
Example: Illustrative 6-inch strainer, half blocked. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 100.00 m³/h |
| Pipe (inlet) diameter | 150.00 mm |
| Clean strainer loss coefficient | 2.5000 - |
| Fluid density | 1,000.0 kg/m³ |
| Fraction of screen open area blocked | 50.000 % |
| Differential pressure alarm | 50.000 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pipe velocity | 1.5719 m/s |
| Clean pressure drop | 3.0886 kPa |
| Pressure drop at that clogging | 12.354 kPa |
| Clogging at the alarm | 75.146 % |
Open this example in the calculator and change any input.
Formula
\(\Delta p_0 = K\frac{\rho v^2}{2}, \quad \Delta p_c = \frac{\Delta p_0}{(1 - c)^2}, \quad c_{al} = 1 - \sqrt{\frac{\Delta p_0}{\Delta p_{al}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow | m³/s |
| \(D\) | Pipe (inlet) diameter | m |
| \(K\) | Clean strainer loss coefficient | - |
| \(\rho\) | Fluid density | kg/m³ |
| \(c\) | Fraction of screen open area blocked | - |
| \(\Delta p_{al}\) | Differential pressure alarm | Pa |
| \(v\) | Pipe velocity | m/s |
| \(\Delta p_0\) | Clean pressure drop | Pa |
| \(\Delta p_c\) | Pressure drop at that clogging | Pa |
| \(c_{al}\) | Clogging at the alarm | - |
Method and standards
Strainer loss.
Where it is used
- Strainer selection and alarm setting.
- Pump suction protection.
Common mistakes
- Taking the clean drop as the design drop.
- Ignoring suction NPSH with clogging.
Assumptions and limits
- Screen loss dominates; incompressible flow.
References
- Loss coefficient with open-area scaling
- Crane Technical Paper 410
- Flow of Fluids through Valves
- Fittings and Pipe (Crane)
Questions and answers
Why does pressure drop rise so fast near full clogging?
Velocity through the remaining open area rises as the blockage grows and loss goes with velocity squared: 50 % blocked gives four times the clean drop.
Where are pump suction strainers a problem?
A clogging suction strainer eats into NPSH margin and can make the pump cavitate.
What do the defaults represent?
An illustrative 6-inch strainer (K = 2.5) passing 100 m³/h of water, half blocked, with a 0.5 bar alarm.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.