FireCADCalc

Pipes in Series and Parallel: Equivalent Pipe and Flow Split

Equivalent length of pipes in series (Dupuit) and the equivalent diameter and flow shares of the same pipes in parallel, for equal friction factors.

Inputs

Examples: Illustrative 300 mm and 250 mm pipesThree pipesEqual pipes

Accepted: 0.1 to 1,000,000 m
Accepted: 5 to 10,000 mm
Accepted: 0.1 to 1,000,000 m
Accepted: 5 to 10,000 mm
Accepted: 0 to 1,000,000 m
Accepted: 5 to 10,000 mm

Results

With the same friction factor, head loss is proportional to L·Q²/D⁵. In series the flow is common and losses add, so the pipes equal one pipe of diameter D₁ and length D₁⁵·ΣL_i/D_i⁵ (Dupuit's equation). In parallel the head loss is common and flows add, each proportional to D^2.5/√L; the equivalent single pipe of length L₁ has diameter (√L₁·ΣD_i^2.5/√L_i)^0.4. Different roughness or Reynolds numbers change the friction factors; iterate with the Darcy–Weisbach calculator for accuracy.

Series: equivalent length of diameter D₁11,786m
Parallel: equivalent diameter of length L₁251.48mm
Parallel: share of flow in pipe 156.406%
Parallel: share in pipe 230.721%
Parallel: share in pipe 312.873%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 300 mm and 250 mm pipes. The inputs, in the units selected above:

InputValue
Length, pipe 1300.00 m
Diameter, pipe 1300.00 mm
Length, pipe 2200.00 m
Diameter, pipe 2250.00 mm
Length, pipe 3 (0 = none)0 m
Diameter, pipe 3200.00 mm

Applying the formula below gives:

ResultValue
Series: equivalent length of diameter D₁797.66 m
Parallel: equivalent diameter of length L₁377.52 mm
Parallel: share of flow in pipe 156.293 %
Parallel: share in pipe 243.707 %
Parallel: share in pipe 30 %

Open this example in the calculator and change any input.

Formula

\(L_e = D_1^5\sum\frac{L_i}{D_i^5}, \quad \frac{q_i}{Q} = \frac{D_i^{2.5}/\sqrt{L_i}}{\sum D_j^{2.5}/\sqrt{L_j}}\)

Variables

Symbol Meaning SI unit
\(L_1\) Length, pipe 1 m
\(D_1\) Diameter, pipe 1 m
\(L_2\) Length, pipe 2 m
\(D_2\) Diameter, pipe 2 m
\(L_3\) Length, pipe 3 (0 = none) m
\(D_3\) Diameter, pipe 3 m
\(L_e\) Series: equivalent length of diameter D₁ m
\(D_e\) Parallel: equivalent diameter of length L₁ m
\(q_1/Q\) Parallel: share of flow in pipe 1 -
\(q_2/Q\) Parallel: share in pipe 2 -
\(q_3/Q\) Parallel: share in pipe 3 -

Method and standards

Series and parallel pipes.

Where it is used

  • Water mains and process piping networks.
  • Fluid mechanics examinations.

Common mistakes

  • Adding diameters instead of conveyance.
  • Ignoring different friction factors.

Assumptions and limits

  • Equal friction factors; minor losses neglected.

References

  • Dupuit's equivalent pipe and parallel pipe relations with a common friction factor

Questions and answers

What single 300 mm pipe equals 300 m of 300 mm plus 200 m of 250 mm in series?

About 798 m of 300 mm pipe.

How does flow split between them in parallel?

About 56 % through the 300 mm pipe and 44 % through the 250 mm pipe.

What do the defaults represent?

An illustrative 300 m of 300 mm pipe with 200 m of 250 mm pipe, in series and in parallel.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.