FireCADCalc

Pipe Velocity and Pipe Size

Fluid velocity in a pipe from the flow and inside diameter, and the inside diameter needed for a target velocity, with mass flow and velocity pressure.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliserThermic fluid heatingPump

Inputs

Examples: Water 50 m³/h in DN100 (102.3 mm)Feedwater 120 m³/h, DN150 (154.1 mm), target 2.5 m/sAir 2 m³/s in a 400 mm duct, target 12 m/s

Results

Velocity15.915m/s
Inside diameter for the target velocity460.66mm
Flow area0.12566m²
Mass flow8,640.0kg/h
Velocity pressure ρv²/2151.98Pa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Water 50 m³/h in DN100 (102.3 mm). The inputs, in the units selected above:

InputValue
Volume flow50.000 m³/h
Pipe inside diameter102.30 mm
Target velocity for sizing (0 = skip)0 m/s
Fluid density998.20 kg/m³

Applying the formula below gives:

ResultValue
Velocity1.6898 m/s
Flow area0.008219 m²
Mass flow49,910 kg/h
Velocity pressure ρv²/21,425.1 Pa

Open this example in the calculator and change any input.

Formula

\(v = \frac{4Q}{\pi D^2} \qquad D_{req} = \sqrt{\frac{4Q}{\pi v_t}} \qquad \dot m = \rho\,Q \qquad p_d = \frac{\rho\,v^2}{2}\)

Variables

Symbol Meaning SI unit
\(Q\) volume flow m³/s
\(D\) pipe inside diameter m
\(v_t\) target velocity for sizing m/s
\(\rho\) fluid density kg/m³
\(v\) mean velocity m/s
\(D_{req}\) inside diameter for the target velocity m
\(A\) flow area m²
\(\dot m\) mass flow kg/s
\(p_d\) velocity pressure Pa

Method and standards

Continuity for a full circular pipe with a uniform mean velocity.

Where it is used

  • Quick checks of line sizes for water, steam and air.
  • Verifying velocity limits for erosion and noise.
  • Choosing a size before a pressure-drop check.

Common mistakes

  • Using nominal size instead of the actual bore of the schedule.
  • Volume flow at the wrong pressure for gases and steam.
  • Ignoring the velocity limits of the fluid and service.

Assumptions and limits

  • Full pipe, single phase.
  • The required diameter is exact; choose the next standard pipe size whose bore is at least that.
  • For gases and steam use the volume flow at the line pressure and temperature.

References

  • Continuity equation

Questions and answers

How do I find the velocity in a pipe?

v = 4Q/(πD²). 50 m³/h in a pipe of 102.3 mm bore flows at 1.69 m/s.

Which diameter do I enter?

The inside diameter: outside diameter minus twice the wall thickness. A DN100 schedule 40 pipe has a bore of 102.3 mm, not 100 mm.

What velocity should I design for?

The calculator does not suggest one. Use the limits of your company standard or project specification for the service; they depend on the fluid, erosion, noise and the pressure drop you can afford.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.