Surface Condensation Check: Inside Surface Temperature vs Dew Point

Inside surface temperature of a wall, roof or window from its U-value and the surface resistance, compared with the room dew point to check for condensation.

Inputs

Examples: Single glazing, 20 °C 60 %, −5 °CInsulated wall, 24 °C 50 %, −20 °CCold steel bridge behind furniture

Your standard's value; 0.13 m²K/W is common for walls with horizontal heat flow, higher for corners and behind furniture.

Results

Inside surface temperature10.900°C
Room dew point12.008°C
Surface above dew point (negative: condensation)-1.1076K
Highest room RH without condensation55.756%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Single glazing, 20 °C 60 %, −5 °C. The inputs, in the units selected above:

InputValue
Room temperature20.000 °C
Room relative humidity60.000 %
Outside temperature-5.0000 °C
U-value of the element2.8000 W/(m²·K)
Inside surface resistance0.13000 m²·K/W

Applying the formula below gives:

ResultValue
Inside surface temperature10.900 °C
Room dew point12.008 °C
Surface above dew point (negative: condensation)-1.1076 K
Highest room RH without condensation55.756 %

Open this example in the calculator and change any input.

Formula

\(T_{si} = T_i - U R_{si}(T_i - T_o)\)

Variables

Symbol Meaning SI unit
\(T_i\) Room temperature K
\(\varphi_i\) Room relative humidity -
\(T_o\) Outside temperature K
\(U\) U-value of the element W/(m²·K)
\(R_{si}\) Inside surface resistance m²·K/W
\(T_{si}\) Inside surface temperature K
\(T_{dp}\) Room dew point K
\(\Delta T\) Surface above dew point (negative: condensation) K
\(\varphi_{max}\) Highest room RH without condensation -

Method and standards

Series resistances.

Where it is used

  • Control rooms, battery rooms and cold stores.
  • Envelope checks.

Common mistakes

  • Using the outside resistance.
  • Average U across a bridge.

Assumptions and limits

  • Steady state.
  • The dew point depends only on the room's vapour pressure, so barometric pressure does not enter the check.

References

  • Steady one-dimensional conduction T_si = T_i − U R_si (T_i − T_o); dew point over water or ice from IAPWS

Questions and answers

Single glazing U 2.8 at 20 °C inside, −5 °C outside?

The glass surface is about 10.9 °C while the room dew point at 60 % is 12 °C: it condenses.

How to avoid it?

Lower U (insulate or double glaze), lower room humidity or warm the surface.

Thermal bridges?

Use the bridge's local U; corners and steel are coldest.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.