Worked example
Example: Single glazing, 20 °C 60 %, −5 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room temperature | 20.000 °C |
| Room relative humidity | 60.000 % |
| Outside temperature | -5.0000 °C |
| U-value of the element | 2.8000 W/(m²·K) |
| Inside surface resistance | 0.13000 m²·K/W |
Applying the formula below gives:
| Result | Value |
|---|---|
| Inside surface temperature | 10.900 °C |
| Room dew point | 12.008 °C |
| Surface above dew point (negative: condensation) | -1.1076 K |
| Highest room RH without condensation | 55.756 % |
Open this example in the calculator and change any input.
Formula
\(T_{si} = T_i - U R_{si}(T_i - T_o)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_i\) | Room temperature | K |
| \(\varphi_i\) | Room relative humidity | - |
| \(T_o\) | Outside temperature | K |
| \(U\) | U-value of the element | W/(m²·K) |
| \(R_{si}\) | Inside surface resistance | m²·K/W |
| \(T_{si}\) | Inside surface temperature | K |
| \(T_{dp}\) | Room dew point | K |
| \(\Delta T\) | Surface above dew point (negative: condensation) | K |
| \(\varphi_{max}\) | Highest room RH without condensation | - |
Method and standards
Series resistances.
Where it is used
- Control rooms, battery rooms and cold stores.
- Envelope checks.
Common mistakes
- Using the outside resistance.
- Average U across a bridge.
Assumptions and limits
- Steady state.
- The dew point depends only on the room's vapour pressure, so barometric pressure does not enter the check.
References
- Steady one-dimensional conduction T_si = T_i − U R_si (T_i − T_o); dew point over water or ice from IAPWS
Questions and answers
Single glazing U 2.8 at 20 °C inside, −5 °C outside?
The glass surface is about 10.9 °C while the room dew point at 60 % is 12 °C: it condenses.
How to avoid it?
Lower U (insulate or double glaze), lower room humidity or warm the surface.
Thermal bridges?
Use the bridge's local U; corners and steel are coldest.