Cooling Coil Bypass Factor, ADP and Sensible Heat Ratio

Bypass and contact factors of a cooling coil from entering, leaving and apparatus dew point temperatures, with the leaving humidity and the sensible heat ratio.

Air conditioning and chillers

Inputs

Examples: 27 °C 50 % entering, 13 °C leaving, ADP 10 °CFresh air coil 35 °C 60 %, leaving 14 °C, ADP 11 °CDry climate 32 °C 20 %, leaving 18 °C, ADP 12 °C (dry coil)Saturated 24 °C entering, leaving 14 °C, ADP 10 °C (line above saturation)

Results

Bypass factor12.500%
Contact factor (1 − BF)87.500%
Leaving humidity ratio9.8246g/kg
Leaving relative humidity98.548%
Sensible heat ratio41.908%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 27 °C 50 % entering, 13 °C leaving, ADP 10 °C. The inputs, in the units selected above:

InputValue
Atmospheric pressure101.33 kPa
Entering air dry bulb27.000 °C
Entering relative humidity50.000 %
Leaving air dry bulb13.000 °C
Apparatus dew point (coil surface)10.000 °C

Applying the formula below gives:

ResultValue
Bypass factor17.647 %
Contact factor (1 − BF)82.353 %
Leaving humidity ratio8.2514 g/kg
Leaving relative humidity88.562 %
Sensible heat ratio65.942 %

Open this example in the calculator and change any input.

Formula

\(BF = \frac{T_2 - T_{ADP}}{T_1 - T_{ADP}}, \quad CF = 1 - BF\)

\(W_2 = W_{ADP} + BF (W_1 - W_{ADP})\)

\(SHR = \frac{h(T_1, W_2) - h(T_2, W_2)}{h(T_1, W_1) - h(T_2, W_2)}\)

Variables

Symbol Meaning SI unit
\(p\) atmospheric pressure Pa
\(T_1\) entering dry bulb K
\(\phi_1\) entering relative humidity -
\(T_2\) leaving dry bulb K
\(T_{ADP}\) apparatus dew point K
\(W_1\) entering humidity ratio kg/kg
\(W_{ADP}\) saturation humidity ratio at the ADP kg/kg
\(h\) moist air enthalpy (ASHRAE) J/kg
\(BF\) bypass factor -
\(CF\) contact factor -
\(W_2\) leaving humidity ratio kg/kg
\(\phi_2\) leaving relative humidity -
\(SHR\) sensible heat ratio -

Method and standards

On the psychrometric chart the coil process is a straight line from the entering state towards the apparatus dew point; the bypass factor locates the leaving state on it. The sensible heat ratio splits the enthalpy drop into sensible and latent parts.

Where it is used

  • Checking coil selections and leaving conditions.
  • Explaining humidity problems in conditioned spaces.
  • Estimating latent removal.

Common mistakes

  • Using wet bulb instead of ADP.
  • Assuming a fixed bypass factor across face velocities.
  • Ignoring fan heat after the coil.

Assumptions and limits

  • Straight-line coil process; ADP from the coil maker or a test.
  • Where that line from a near-saturated entering state passes above the saturation curve, the leaving humidity is capped at saturation, with a note.
  • SHR convention: the sensible part is h(T₁, W₂) − h(T₂, W₂), the cooling at the leaving humidity; the rest of the total enthalpy drop is latent.

References

  • Bypass factor method (ASHRAE psychrometrics)

Questions and answers

What is the bypass factor of a coil cooling 27 °C air to 13 °C with ADP 10 °C?

(13 − 10)/(27 − 10) = 0.18; contact factor 0.82. With 50 % RH entering, the sensible heat ratio is about 0.66.

What does the bypass factor mean?

The share of air that behaves as if it missed the coil surface; more rows and lower face velocity reduce it.

What if the entering air is drier than the ADP saturation?

The coil cools without condensing and the sensible heat ratio is 1.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.