Worked example
Example: 27 °C 50 % entering, 13 °C leaving, ADP 10 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Atmospheric pressure | 101.33 kPa |
| Entering air dry bulb | 27.000 °C |
| Entering relative humidity | 50.000 % |
| Leaving air dry bulb | 13.000 °C |
| Apparatus dew point (coil surface) | 10.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Bypass factor | 17.647 % |
| Contact factor (1 − BF) | 82.353 % |
| Leaving humidity ratio | 8.2514 g/kg |
| Leaving relative humidity | 88.562 % |
| Sensible heat ratio | 65.942 % |
Open this example in the calculator and change any input.
Formula
\(BF = \frac{T_2 - T_{ADP}}{T_1 - T_{ADP}}, \quad CF = 1 - BF\)
\(W_2 = W_{ADP} + BF (W_1 - W_{ADP})\)
\(SHR = \frac{h(T_1, W_2) - h(T_2, W_2)}{h(T_1, W_1) - h(T_2, W_2)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | atmospheric pressure | Pa |
| \(T_1\) | entering dry bulb | K |
| \(\phi_1\) | entering relative humidity | - |
| \(T_2\) | leaving dry bulb | K |
| \(T_{ADP}\) | apparatus dew point | K |
| \(W_1\) | entering humidity ratio | kg/kg |
| \(W_{ADP}\) | saturation humidity ratio at the ADP | kg/kg |
| \(h\) | moist air enthalpy (ASHRAE) | J/kg |
| \(BF\) | bypass factor | - |
| \(CF\) | contact factor | - |
| \(W_2\) | leaving humidity ratio | kg/kg |
| \(\phi_2\) | leaving relative humidity | - |
| \(SHR\) | sensible heat ratio | - |
Method and standards
On the psychrometric chart the coil process is a straight line from the entering state towards the apparatus dew point; the bypass factor locates the leaving state on it. The sensible heat ratio splits the enthalpy drop into sensible and latent parts.
Where it is used
- Checking coil selections and leaving conditions.
- Explaining humidity problems in conditioned spaces.
- Estimating latent removal.
Common mistakes
- Using wet bulb instead of ADP.
- Assuming a fixed bypass factor across face velocities.
- Ignoring fan heat after the coil.
Assumptions and limits
- Straight-line coil process; ADP from the coil maker or a test.
- Where that line from a near-saturated entering state passes above the saturation curve, the leaving humidity is capped at saturation, with a note.
- SHR convention: the sensible part is h(T₁, W₂) − h(T₂, W₂), the cooling at the leaving humidity; the rest of the total enthalpy drop is latent.
References
- Bypass factor method (ASHRAE psychrometrics)
Questions and answers
What is the bypass factor of a coil cooling 27 °C air to 13 °C with ADP 10 °C?
(13 − 10)/(27 − 10) = 0.18; contact factor 0.82. With 50 % RH entering, the sensible heat ratio is about 0.66.
What does the bypass factor mean?
The share of air that behaves as if it missed the coil surface; more rows and lower face velocity reduce it.
What if the entering air is drier than the ADP saturation?
The coil cools without condensing and the sensible heat ratio is 1.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.