FireCADCalc

Boiler Blowdown Set by Water Limits (TDS, Silica, Alkalinity)

Blowdown needed to keep boiler water TDS, silica and alkalinity within your limits from the feedwater analysis; the highest of the three governs.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserBoilerWater treatment plant

Inputs

Examples: Feed TDS 100, silica 2, alkalinity 40 ppm; limits 3000 / 100 / 600Feed 300 / 5 / 80; limits 3500 / 150 / 700High pressure: feed 5 / 0.2 / 2; limits 100 / 2 / 20

Feedwater

Boiler water limits (from your boiler maker or water chemistry standard)

Results

alkalinity sets the blowdown.

Blowdown needed, share of steam12.903%
Blowdown for TDS9.3750%
Blowdown for silica3.4483%
Blowdown for alkalinity12.903%
Cycles of concentration8.7500

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Feed TDS 100, silica 2, alkalinity 40 ppm; limits 3000 / 100 / 600. The inputs, in the units selected above:

InputValue
TDS100.00 ppm
Silica, as SiO₂2.0000 ppm
Total alkalinity, as CaCO₃40.000 ppm
TDS limit3,000.0 ppm
Silica limit100.00 ppm
Total alkalinity limit600.00 ppm

Applying the formula below gives:

ResultValue
Blowdown needed, share of steam7.1429 %
Blowdown for TDS3.4483 %
Blowdown for silica2.0408 %
Blowdown for alkalinity7.1429 %
Cycles of concentration15.000

Open this example in the calculator and change any input.

Formula

\(b_i = \frac{f_i}{L_i - f_i} \quad (i = TDS,\ SiO_2,\ alk) \qquad b = \max_i b_i \qquad N = \frac{1 + b}{b}\)

Variables

Symbol Meaning SI unit
\(f_{TDS}\), \(f_{SiO_2}\), \(f_{alk}\) feedwater TDS, silica, alkalinity –
\(L_{TDS}\), \(L_{SiO_2}\), \(L_{alk}\) boiler water limits –
\(b\) blowdown needed, share of steam –
\(b_{TDS}\) blowdown for TDS –
\(b_{SiO_2}\) blowdown for silica –
\(b_{alk}\) blowdown for alkalinity –
\(N\) cycles of concentration –

Method and standards

Steady mass balance of a conserved solute in the drum: what enters with the feedwater leaves with the blowdown at the boiler water concentration (steam carries none).

Where it is used

  • Setting continuous blowdown and TDS controllers.
  • Choosing make-up treatment: which parameter is worth removing.
  • Water and fuel budgets of the boiler house.

Common mistakes

  • Controlling on TDS when silica or alkalinity is the real limit.
  • Using limits for a lower pressure than the boiler runs at.
  • Forgetting that alkalinity partly breaks down to CO₂, which leaves with the steam.

Assumptions and limits

  • Steam carries no solids; parameters conserved in the drum; steady operation. At high pressure silica is carried by the steam; a note appears when silica governs.
  • A feedwater value of zero leaves that parameter out of the comparison; when two give the same blowdown, both are named.

References

  • Dissolved-solids mass balance of the boiler drum

Questions and answers

Which parameter sets the blowdown?

The one that reaches its limit first. With feedwater of 100 ppm TDS, 2 ppm silica and 40 ppm alkalinity, and limits of 3000, 100 and 600 ppm, alkalinity needs 7.1 % blowdown, more than TDS (3.4 %) or silica (2.0 %); the boiler runs at 15 cycles.

Where do the limits come from?

From your boiler maker or a water chemistry standard for the boiler pressure; they fall steeply as pressure rises. This calculator takes them as inputs.

How do I lower the blowdown?

Treat the limiting parameter in the make-up (dealkalisation for alkalinity, RO for silica and TDS) or return more condensate.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.