Worked example
Example: Illustrative 1700 kg/s, 227 C, 6.9 MPa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total feedwater flow | 6,120,000 kg/h |
| Feedwater temperature | 227.00 °C |
| Steam pressure at the generator outlet | 6.9000 MPa |
| Steam quality (1 − moisture carry-over) | 99.750 % |
| Blowdown flow | 18,000 kg/h |
| Reactor coolant pump heat | 16.000 MW |
| Primary heat losses and letdown corrections | 2.0000 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam enthalpy | 2,770.1 kJ/kg |
| Feedwater enthalpy | 977.13 kJ/kg |
| Steam generator duty | 3,040.5 MW |
| Reactor (core) thermal power | 3,026.5 MW |
Open this example in the calculator and change any input.
Formula
\(\dot Q_{SG} = (\dot m_{fw} - \dot m_{bd})(h_s - h_{fw}) + \dot m_{bd}(h_f - h_{fw}), \quad \dot Q_{core} = \dot Q_{SG} - \dot Q_{pump} + \dot Q_{loss}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_{fw}\) | Total feedwater flow | kg/s |
| \(T_{fw}\) | Feedwater temperature | K |
| \(p_s\) | Steam pressure at the generator outlet | Pa |
| \(x\) | Steam quality (1 − moisture carry-over) | - |
| \(\dot m_{bd}\) | Blowdown flow | kg/s |
| \(\dot Q_{pump}\) | Reactor coolant pump heat | W |
| \(\dot Q_{loss}\) | Primary heat losses and letdown corrections | W |
| \(h_s\) | Steam enthalpy | J/kg |
| \(h_{fw}\) | Feedwater enthalpy | J/kg |
| \(\dot Q_{SG}\) | Steam generator duty | W |
| \(\dot Q_{core}\) | Reactor (core) thermal power | W |
Method and standards
Secondary heat balance.
Where it is used
- Daily power calibration of nuclear instrumentation.
- Power uprate measurement studies.
Common mistakes
- Forgetting pump heat.
- Using dry saturated steam when moisture carry-over is measured.
Assumptions and limits
- Steady state; all steam generators lumped.
References
- Secondary-side calorimetric heat balance
Questions and answers
Why is reactor power measured on the secondary side?
Feedwater flow, temperature and steam pressure can be measured far more accurately than the primary flow, giving power to within about 1–2 %, or under 0.5 % with ultrasonic flow meters.
Why subtract pump heat?
Reactor coolant pumps add several megawatts of heat that the steam generators also remove; it did not come from the core.
What do the defaults represent?
An illustrative plant: 1,700 kg/s feedwater at 227 °C, steam at 6.9 MPa with 0.25 % moisture, 5 kg/s blowdown, 16 MW pump heat and 2 MW losses.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.