Calorimetric (Secondary Heat Balance) Reactor Thermal Power

Reactor thermal power from a secondary heat balance of the steam generators: feedwater flow and temperature, steam pressure and moisture, blowdown, pump heat.

Thermal power plant

Inputs

Examples: Illustrative 1700 kg/s, 227 C, 6.9 MPaTwo-loop 1000 kg/s, 220 C, 6.3 MPa, dry steamSmall 300 kg/s, 210 C, 5.5 MPa

Accepted: 360 to 18,000,000 kg/h
Accepted: 6.85 to 326.85 °C
Accepted: 0.1 to 20 MPa
Accepted: 90 to 100 %
Accepted: 0 to 360,000 kg/h
Accepted: 0 to 100 MW
Accepted: 0 to 100 MW

Results

Q_SG = (ṁ_fw − ṁ_bd)(h_s − h_fw) + ṁ_bd(h_f − h_fw); core power = Q_SG − pump heat + primary losses. Feedwater flow measurement is the largest uncertainty (venturi fouling, or ultrasonic correction). Water and steam properties from IAPWS-IF97.

Steam enthalpy2,786.5kJ/kg
Feedwater enthalpy898.98kJ/kg
Steam generator duty564.66MW
Reactor (core) thermal power563.16MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1700 kg/s, 227 C, 6.9 MPa. The inputs, in the units selected above:

InputValue
Total feedwater flow6,120,000 kg/h
Feedwater temperature227.00 °C
Steam pressure at the generator outlet6.9000 MPa
Steam quality (1 − moisture carry-over)99.750 %
Blowdown flow18,000 kg/h
Reactor coolant pump heat16.000 MW
Primary heat losses and letdown corrections2.0000 MW

Applying the formula below gives:

ResultValue
Steam enthalpy2,770.1 kJ/kg
Feedwater enthalpy977.13 kJ/kg
Steam generator duty3,040.5 MW
Reactor (core) thermal power3,026.5 MW

Open this example in the calculator and change any input.

Formula

\(\dot Q_{SG} = (\dot m_{fw} - \dot m_{bd})(h_s - h_{fw}) + \dot m_{bd}(h_f - h_{fw}), \quad \dot Q_{core} = \dot Q_{SG} - \dot Q_{pump} + \dot Q_{loss}\)

Variables

Symbol Meaning SI unit
\(\dot m_{fw}\) Total feedwater flow kg/s
\(T_{fw}\) Feedwater temperature K
\(p_s\) Steam pressure at the generator outlet Pa
\(x\) Steam quality (1 − moisture carry-over) -
\(\dot m_{bd}\) Blowdown flow kg/s
\(\dot Q_{pump}\) Reactor coolant pump heat W
\(\dot Q_{loss}\) Primary heat losses and letdown corrections W
\(h_s\) Steam enthalpy J/kg
\(h_{fw}\) Feedwater enthalpy J/kg
\(\dot Q_{SG}\) Steam generator duty W
\(\dot Q_{core}\) Reactor (core) thermal power W

Method and standards

Secondary heat balance.

Where it is used

  • Daily power calibration of nuclear instrumentation.
  • Power uprate measurement studies.

Common mistakes

  • Forgetting pump heat.
  • Using dry saturated steam when moisture carry-over is measured.

Assumptions and limits

  • Steady state; all steam generators lumped.

References

  • Secondary-side calorimetric heat balance

Questions and answers

Why is reactor power measured on the secondary side?

Feedwater flow, temperature and steam pressure can be measured far more accurately than the primary flow, giving power to within about 1–2 %, or under 0.5 % with ultrasonic flow meters.

Why subtract pump heat?

Reactor coolant pumps add several megawatts of heat that the steam generators also remove; it did not come from the core.

What do the defaults represent?

An illustrative plant: 1,700 kg/s feedwater at 227 °C, steam at 6.9 MPa with 0.25 % moisture, 5 kg/s blowdown, 16 MW pump heat and 2 MW losses.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.