FireCADCalc

Emission Rate per GJ from Concentration, O₂ and F-Factor

Emission rate in g per GJ of fuel heat from a dry stack concentration at 0 °C, the dry O₂ and the fuel's dry F-factor (US EPA Method 19, Eq. 19-1).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolStack and chimney

Inputs

Examples: 500 mg/Nm3 at 6 % O2Dust 50 mg/Nm3 at 11 %

Results

Concentration at 20 °C46.589mg/m³
Emission rate25.769g/GJ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 mg/Nm3 at 6 % O2. The inputs, in the units selected above:

InputValue
Pollutant concentration (dry, 0 °C, 1 atm)500.00 mg/Nm³
Oxygen in dry flue gas6.0000 %
Dry F-factor (dscm per GJ at 20 °C)264.00 -

Applying the formula below gives:

ResultValue
Concentration at 20 °C465.89 mg/m³
Emission rate172.52 g/GJ

Open this example in the calculator and change any input.

Formula

\(C_{20} = C_d \frac{273.15}{293.15}, \quad E = C_{20} F_d \frac{20.9}{20.9 - \%O_{2,d}}\)

Variables

Symbol Meaning SI unit
\(C_d\) Pollutant concentration (dry, 0 °C, 1 atm) kg/m³
\(O_{2,d}\) Oxygen in dry flue gas -
\(F_d\) Dry F-factor (dscm per GJ at 20 °C) -
\(C_{20}\) Concentration at 20 °C kg/m³
\(E\) Emission rate kg/J

Method and standards

US EPA Method 19.

Where it is used

  • Emission reports per heat input.
  • Comparing permits in different units.

Common mistakes

  • Wet O₂ with dry concentration.

Assumptions and limits

  • Dry basis throughout.
  • EPA F-factors are per unit of gross (higher) calorific value, so the emission rate is per GJ of HHV.
  • The F-factor is entered in dscm per GJ at 20 °C in every unit system.

References

  • US EPA Method 19 Eq. 19-1
  • E = C_d F_d 20.9/(20.9 − %O₂d); 0 °C to 20 °C by ideal gas

Questions and answers

Why g/GJ?

It compares boilers and fuels independent of dilution and size.

Why convert 0 °C to 20 °C?

Method 19 F-factors use 20 °C; a normal cubic metre at 0 °C holds more gas.

lb/MMBtu?

Divide g/GJ by 429.9 (453.59 g/lb over 1.0551 GJ/MMBtu), or choose an FPS display for the output. The F-factor input is in dscm/GJ; convert EPA table values in dscf/MMBtu by multiplying by 0.02684.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.