Worked example
Example: Indian coal, 18.6 MJ/kg, 50 t/h, 8 000 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon, as fired, by mass | 45.000 % |
| Hydrogen, as fired, by mass | 3.5000 % |
| Moisture, as fired, by mass | 10.000 % |
| Gross calorific value, as fired | 18,600 kJ/kg |
| Fraction of carbon oxidised | 100.00 % |
| Fuel firing rate (0 = skip) | 50,000 kg/h |
| Operating hours per year | 8,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| CO₂ per kg of fuel | 1.6488 kg/kg |
| CO₂ per unit of heat, on NCV (IPCC basis) | 93.725 kg/GJ |
| CO₂ per unit of heat, on GCV | 88.647 kg/GJ |
| Net calorific value | 17,592 kJ/kg |
| CO₂ emitted | 82.441 t/h |
| CO₂ per year | 659,530 t |
Open this example in the calculator and change any input.
Formula
\(e_m = C \cdot \frac{M_{CO_2}}{M_C} \cdot f_{ox} = 3.664\;C\,f_{ox}\)
\(NCV = GCV - h_{fg,25}\left(\frac{M_{H_2O}}{M_{H_2}}H + M\right) \qquad e_{NCV} = \frac{e_m}{NCV} \qquad e_{GCV} = \frac{e_m}{GCV}\)
\(\dot m_{CO_2} = \dot m_f\,e_m \qquad m_{CO_2} = \dot m_{CO_2}\,t_{op}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | carbon in the fuel as fired, by mass | – |
| \(H\) | hydrogen in the fuel as fired | – |
| \(M\) | moisture in the fuel as fired | – |
| \(GCV\) | gross calorific value as fired | J/kg |
| \(f_{ox}\) | fraction of carbon oxidised | – |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(t_{op}\) | operating hours per year | s |
| \(e_m\) | CO₂ per kg of fuel | kg/kg |
| \(e_{NCV}\) | CO₂ per unit of heat on NCV | kg/J |
| \(e_{GCV}\) | CO₂ per unit of heat on GCV | kg/J |
| \(NCV\) | net calorific value | J/kg |
| \(\dot m_{CO_2}\) | CO₂ emitted | kg/s |
| \(m_{CO_2}\) | CO₂ per year | kg |
| \(M_{CO_2}\), \(M_C\), \(M_{H_2O}\), \(M_{H_2}\) | molar masses (44.009, 12.011, 18.015, 2.016) | kg/kmol |
| \(h_{fg,25}\) | latent heat of water at 25 °C (2 441.7 kJ/kg, IF97) | J/kg |
Method and standards
The carbon-content method of the IPCC 2006 Guidelines (Vol. 2, Energy): CO₂ = carbon × 44/12 × fraction oxidised, here with exact IUPAC molar masses (44.009/12.011). The IPCC default fraction oxidised is 1. The net calorific value is the gross value less the latent heat at 25 °C of the water formed from hydrogen and the fuel moisture, the ASME PTC 4 convention; the latent heat comes from FireCAD's IAPWS-IF97.
Where it is used
- Carbon accounting of boilers and furnaces.
- Comparing fuels by CO2 per GJ.
- Emission reports and carbon cost estimates.
Common mistakes
- Using NCV in one place and GCV in another.
- Using a default factor when the fuel analysis is available.
- Counting biomass CO2 the same way as fossil CO2 where rules treat it differently.
Assumptions and limits
- Carbon content as fired, on the same moisture basis as the calorific value and the firing rate.
- All carbon that is oxidised ends as CO₂; carbonates in the ash and limestone used for desulphurisation add CO₂ not counted here.
- The net value is the PTC 4 style deduction (latent heat at 25 °C, no constant-volume oxygen and nitrogen correction). Net values measured to ISO 1928 or used in IPCC tables may differ slightly, so \(e_{NCV}\) depends on this convention.
- For natural gas enter the analysis by mass (methane: 74.9 % carbon, 25.1 % hydrogen).
References
- IPCC 2006 Guidelines Vol. 2 Ch. 1–2 (carbon-content method)
- IUPAC atomic weights
- IAPWS R7-97(2012) IF97 (latent heat)
Questions and answers
How much CO₂ does 1 kg of coal produce?
Each kg of carbon becomes 44.009/12.011 = 3.664 kg of CO₂. An Indian coal with 45 % carbon gives 1.65 kg CO₂ per kg, or 93.7 kg per GJ on its net calorific value.
Why per GJ on NCV?
The IPCC 2006 Guidelines and most national inventories state emission factors per unit of net calorific value. Indian and US plant data are often on GCV; the calculator gives both.
Is biomass CO₂ counted?
The calculator gives the CO₂ physically released. Under IPCC rules CO₂ from sustainably grown biomass such as bagasse is reported separately and not counted in the energy-sector total.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.