FireCADCalc

U-Value of a Wall or Roof from Its Layers

Thermal transmittance (U-value) of a wall, roof or panel from up to five layers' thickness and conductivity, surface resistances and an air gap.

Inputs

Examples: Plastered brick with 50 mm insulationCold store panel 150 mm PUFCavity wall, five layers

Layer 1

Layer 2

Layer 3

Layer 4

Layer 5

Results

Surface resistances and conductivities from your standard or the material makers; thermal bridges are not included.

Total resistance6.9882m²·K/W
U-value0.14310W/(m²·K)
Heat flow per m²0.007155kW/m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Plastered brick with 50 mm insulation. The inputs, in the units selected above:

InputValue
Layer 1 thickness15.000 mm
Layer 1 conductivity0.72000 W/(m·K)
Layer 2 thickness230.00 mm
Layer 2 conductivity0.84000 W/(m·K)
Layer 3 thickness50.000 mm
Layer 3 conductivity0.035000 W/(m·K)
Layer 4 thickness0 mm
Layer 4 conductivity1.0000 W/(m·K)
Layer 5 thickness0 mm
Layer 5 conductivity1.0000 W/(m·K)
Air gap resistance (0 if none)0 m²·K/W
Inside surface resistance0.13000 m²·K/W
Outside surface resistance0.040000 m²·K/W
Temperature difference (for the heat flow)20.000 K

Applying the formula below gives:

ResultValue
Total resistance1.8932 m²·K/W
U-value0.52820 W/(m²·K)
Heat flow per m²0.010564 kW/m²

Open this example in the calculator and change any input.

Formula

\(U = \frac{1}{R_{si} + \sum d_i/\lambda_i + R_g + R_{se}}\)

Variables

Symbol Meaning SI unit
\(d_{1}\) Layer 1 thickness m
\(\lambda_{1}\) Layer 1 conductivity W/(m·K)
\(d_{2}\) Layer 2 thickness m
\(\lambda_{2}\) Layer 2 conductivity W/(m·K)
\(d_{3}\) Layer 3 thickness m
\(\lambda_{3}\) Layer 3 conductivity W/(m·K)
\(d_{4}\) Layer 4 thickness m
\(\lambda_{4}\) Layer 4 conductivity W/(m·K)
\(d_{5}\) Layer 5 thickness m
\(\lambda_{5}\) Layer 5 conductivity W/(m·K)
\(R_g\) Air gap resistance (0 if none) m²·K/W
\(R_{si}\) Inside surface resistance m²·K/W
\(R_{se}\) Outside surface resistance m²·K/W
\(\Delta T\) Temperature difference (for the heat flow) K
\(R_T\) Total resistance m²·K/W
\(U\) U-value W/(m²·K)
\(q\) Heat flow per m² W/m²

Method and standards

Series resistances.

Where it is used

  • Cold store panels, control room walls and roofs.
  • Heat loss and gain calculations.

Common mistakes

  • mm in the formula.
  • Ignoring thermal bridges.

Assumptions and limits

  • One-dimensional, homogeneous layers.

References

  • Series thermal resistances U = 1/(R_si + Σd/λ + R_g + R_se) (ISO 6946 principle)

Questions and answers

Plastered 230 mm brick with 50 mm insulation?

R about 1.89 m²K/W, U about 0.53 W/m²K.

Where do R_si and R_se come from?

Your standard; 0.13 and 0.04 are common for walls.

Metal fixings through insulation?

They raise U; correct for them as your standard requires.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.