Worked example
Example: Plastered brick with 50 mm insulation. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Layer 1 thickness | 15.000 mm |
| Layer 1 conductivity | 0.72000 W/(m·K) |
| Layer 2 thickness | 230.00 mm |
| Layer 2 conductivity | 0.84000 W/(m·K) |
| Layer 3 thickness | 50.000 mm |
| Layer 3 conductivity | 0.035000 W/(m·K) |
| Layer 4 thickness | 0 mm |
| Layer 4 conductivity | 1.0000 W/(m·K) |
| Layer 5 thickness | 0 mm |
| Layer 5 conductivity | 1.0000 W/(m·K) |
| Air gap resistance (0 if none) | 0 m²·K/W |
| Inside surface resistance | 0.13000 m²·K/W |
| Outside surface resistance | 0.040000 m²·K/W |
| Temperature difference (for the heat flow) | 20.000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total resistance | 1.8932 m²·K/W |
| U-value | 0.52820 W/(m²·K) |
| Heat flow per m² | 0.010564 kW/m² |
Open this example in the calculator and change any input.
Formula
\(U = \frac{1}{R_{si} + \sum d_i/\lambda_i + R_g + R_{se}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(d_{1}\) | Layer 1 thickness | m |
| \(\lambda_{1}\) | Layer 1 conductivity | W/(m·K) |
| \(d_{2}\) | Layer 2 thickness | m |
| \(\lambda_{2}\) | Layer 2 conductivity | W/(m·K) |
| \(d_{3}\) | Layer 3 thickness | m |
| \(\lambda_{3}\) | Layer 3 conductivity | W/(m·K) |
| \(d_{4}\) | Layer 4 thickness | m |
| \(\lambda_{4}\) | Layer 4 conductivity | W/(m·K) |
| \(d_{5}\) | Layer 5 thickness | m |
| \(\lambda_{5}\) | Layer 5 conductivity | W/(m·K) |
| \(R_g\) | Air gap resistance (0 if none) | m²·K/W |
| \(R_{si}\) | Inside surface resistance | m²·K/W |
| \(R_{se}\) | Outside surface resistance | m²·K/W |
| \(\Delta T\) | Temperature difference (for the heat flow) | K |
| \(R_T\) | Total resistance | m²·K/W |
| \(U\) | U-value | W/(m²·K) |
| \(q\) | Heat flow per m² | W/m² |
Method and standards
Series resistances.
Where it is used
- Cold store panels, control room walls and roofs.
- Heat loss and gain calculations.
Common mistakes
- mm in the formula.
- Ignoring thermal bridges.
Assumptions and limits
- One-dimensional, homogeneous layers.
References
- Series thermal resistances U = 1/(R_si + Σd/λ + R_g + R_se) (ISO 6946 principle)
Questions and answers
Plastered 230 mm brick with 50 mm insulation?
R about 1.89 m²K/W, U about 0.53 W/m²K.
Where do R_si and R_se come from?
Your standard; 0.13 and 0.04 are common for walls.
Metal fixings through insulation?
They raise U; correct for them as your standard requires.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.