Ventilation Air to Remove Heat from a Room

Air flow to remove a heat load from a room (switchgear, transformer, pump or turbine room) for an allowed temperature rise, with air changes per hour.

Inputs

Examples: 40 kW switchgear room, 35 °C air, 5 KTransformer 15 kW, 30 °C, 10 K

0 °C or warmer (the moist-air properties used start at 0 °C).

Results

Equipment makers limit room temperature; in hot climates ventilation may not be enough and cooling is needed.

Dry-air mass flow5,213.2kg/h
Air flow at the inlet4,592.5m³/h
Air changes per hour38.271

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 40 kW switchgear room, 35 °C air, 5 K. The inputs, in the units selected above:

InputValue
Heat to remove40.000 kW
Inlet air temperature35.000 °C
Allowed temperature rise5.0000 K
Inlet relative humidity50.000 %
Room volume (for air changes)600.00 m³
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Dry-air mass flow27,718 kg/h
Air flow at the inlet24,887 m³/h
Air changes per hour41.479

Open this example in the calculator and change any input.

Formula

\(\dot m_{da} = \frac{\dot Q}{h(T_1 + \Delta T, W) - h(T_1, W)}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) Heat to remove W
\(T_1\) Inlet air temperature K
\(\Delta T\) Allowed temperature rise K
\(\varphi\) Inlet relative humidity -
\(V_r\) Room volume (for air changes) m³
\(p\) Barometric pressure (absolute) Pa
\(\dot m_{da}\) Dry-air mass flow kg/s
\(\dot V\) Air flow at the inlet m³/s
\(ACH\) Air changes per hour -

Method and standards

Energy balance.

Where it is used

  • Switchgear, transformer, pump and turbine rooms.
  • Battery and DG rooms (heat part).

Common mistakes

  • Using the outlet volume.
  • Short-circuiting between inlet and outlet.

Assumptions and limits

  • Well-mixed room.

References

  • Energy balance on moist air
  • ASHRAE enthalpy (ASHRAE Handbook—Fundamentals ch. 1)

Questions and answers

40 kW with 35 °C air and a 5 K rise?

About 24,900 m³/h, some 41 air changes in a 600 m³ room.

Why does the rise matter so much?

Flow is inversely proportional to it.

Transformer rooms?

Use the transformer's no-load plus load losses as the heat.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.