Worked example
Example: 40 kW switchgear room, 35 °C air, 5 K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat to remove | 40.000 kW |
| Inlet air temperature | 35.000 °C |
| Allowed temperature rise | 5.0000 K |
| Inlet relative humidity | 50.000 % |
| Room volume (for air changes) | 600.00 m³ |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dry-air mass flow | 27,718 kg/h |
| Air flow at the inlet | 24,887 m³/h |
| Air changes per hour | 41.479 |
Open this example in the calculator and change any input.
Formula
\(\dot m_{da} = \frac{\dot Q}{h(T_1 + \Delta T, W) - h(T_1, W)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Heat to remove | W |
| \(T_1\) | Inlet air temperature | K |
| \(\Delta T\) | Allowed temperature rise | K |
| \(\varphi\) | Inlet relative humidity | - |
| \(V_r\) | Room volume (for air changes) | m³ |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\dot m_{da}\) | Dry-air mass flow | kg/s |
| \(\dot V\) | Air flow at the inlet | m³/s |
| \(ACH\) | Air changes per hour | - |
Method and standards
Energy balance.
Where it is used
- Switchgear, transformer, pump and turbine rooms.
- Battery and DG rooms (heat part).
Common mistakes
- Using the outlet volume.
- Short-circuiting between inlet and outlet.
Assumptions and limits
- Well-mixed room.
References
- Energy balance on moist air
- ASHRAE enthalpy (ASHRAE Handbook—Fundamentals ch. 1)
Questions and answers
40 kW with 35 °C air and a 5 K rise?
About 24,900 m³/h, some 41 air changes in a 600 m³ room.
Why does the rise matter so much?
Flow is inversely proportional to it.
Transformer rooms?
Use the transformer's no-load plus load losses as the heat.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.