Ventilation and Fresh Air Heat Load

Sensible, latent and total load of outdoor air brought into a room, from air changes per hour or fresh-air flow and the outdoor and indoor conditions.

Air conditioning and chillers

Inputs

Examples: Control room 600 m³, 2 ACH, 38 °C 45 % outside, 24 °C 50 % insideOffice 300 m³, 3 ACH, 35 °C 70 %, 23 °C 55 %Winter: 1000 m³, 1 ACH, 5 °C 80 %, 21 °C 40 %

Enter a known fresh-air flow (outdoor state) to use it instead of volume × air changes.

Results

Infiltration through doors and leaks adds to this; a negative load means the outdoor air heats or humidifies the room.

Total load (positive = cooling)-7.3297kW
Sensible load-5.6994kW
Latent load-1.6302kW
Outdoor air flow1,000.0m³/h
Dry-air mass flow1,260.3kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Control room 600 m³, 2 ACH, 38 °C 45 % outside, 24 °C 50 % inside. The inputs, in the units selected above:

InputValue
Room volume600.00 m³
Air changes per hour2.0000 -
Outdoor dry bulb38.000 °C
Outdoor relative humidity45.000 %
Indoor dry bulb24.000 °C
Indoor relative humidity50.000 %
Barometric pressure (absolute)101.33 kPa
Fresh-air flow (0 = use the air changes)0 m³/h

Applying the formula below gives:

ResultValue
Total load (positive = cooling)14.296 kW
Sensible load5.2581 kW
Latent load9.0379 kW
Outdoor air flow1,200.0 m³/h
Dry-air mass flow1,321.3 kg/h

Open this example in the calculator and change any input.

Formula

\(\dot V_o = \frac{n\,V_r}{3600}\ \text{or}\ \dot V_f \qquad \dot m_{da} = \frac{\dot V_o}{v_o} \qquad \dot Q_t = \dot m_{da}(h_o - h_i) \qquad \dot Q_s = \dot m_{da}\,[h(T_o, W_i) - h_i] \qquad \dot Q_l = \dot Q_t - \dot Q_s\)

Variables

Symbol Meaning SI unit
\(V_r\) room volume m³
\(n\) air changes per hour 1/h
\(T_o\) outdoor dry bulb K
\(\varphi_o\) outdoor RH –
\(T_i\) indoor dry bulb K
\(\varphi_i\) indoor RH –
\(p\) barometric pressure Pa
\(\dot V_f\) fresh-air flow at the outdoor state (used instead of n V_r when above 0) m³/s
\(\dot Q_t\) total load W
\(\dot Q_s\) sensible load W
\(\dot Q_l\) latent load W
\(\dot V_o\) outdoor air flow m³/s
\(\dot m_{da}\) dry-air flow kg/s
\(h_o, h_i\) outdoor and indoor enthalpy J/kg
\(W_i\) indoor humidity ratio kg/kg
\(v_o\) outdoor specific volume m³/kg

Method and standards

Energy balance on the outdoor air brought to room conditions, with ASHRAE moist-air enthalpy.

Where it is used

  • Control rooms, MCC and battery rooms.
  • Pressurisation air for electrical rooms.
  • Fresh-air requirement checks.

Common mistakes

  • Using the room volume flow at indoor density for outdoor air.
  • Ignoring latent load in humid seasons.
  • Leaving out infiltration through doors.

Assumptions and limits

  • The outdoor air flow is n V_r/3600 from the air changes, or the fresh-air flow entered (at the outdoor state) when that is above zero.

  • Steady state; the outdoor air is fully brought to room conditions.

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics

Questions and answers

What load do 2 air changes bring into a 600 m³ control room?

With 38 °C 45 % outside and 24 °C 50 % inside: 14.3 kW total, of which 5.3 kW sensible and 9.0 kW latent.

Why is the latent part so large?

Humid outdoor air carries much more moisture than the conditioned room; in monsoon climates latent often exceeds sensible.

Does it work for heating?

Yes: in winter the result is negative, meaning heat must be added.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.